D9412GV2/D7412GV2 | Program Entry Guide | 2.0  GV2MAIN 
EN | 33 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
2.7.2  Log Threshold Reports 
Log % Full 
If communication with RPS is unsuccessful, or if no 
phone number is programmed in RPS Ph, the control 
panel generates Log Threshold and Bad Call to Ram. 
This indicates the log is filling and the control panel 
cannot download its events. 
Default: 
Blank 
Selection:  1 to 99, or Blank 
This parameter determines how full the memory log 
can be before initiating a call to RPS at the central 
station. This allows the central station to call the 
control panel and copy the memory log before 
messages are overwritten. 
If there is no RPS Ph programmed, the control panel 
generates the Log Threshold and Bad Call to RPS 
Events immediately. Bad Call to RPS Events are 
logged only locally. If an RPS Ph is programmed, the 
control panel makes multiple attempts to reach RPS 
before sending the reports. Refer to the RPS Ph 
prompt in Section 
Blank disables the Log Threshold and Log Overflow 
Events. These events are not entered in the log or 
reported to the D6500 or D6600 or the local printer. 
explanation of dialing characteristics.  
The control panel continues to log events after the 
Log Threshold Report is sent. When it reaches 100% 
capacity (memory logger is full and previously stored 
events are overwritten), the control panel generates a 
local Log Overflow Event. 
2.7.3  RPS Callback Reports 
When dialing the RPS phone number, the control 
panel makes two attempts to reach RPS. If the 
control panel does not reach RPS on the first two 
attempts, it waits 10 min then tries six more times 
with a 10-min interval between each attempt. One 
hour after the last failed attempt, the control panel 
starts dialing the RPS phone number again. It makes 
two more attempts then waits 10 min and tries six 
more times with 10-min intervals between each 
attempt before generating a Bad Call to RPS Report 
and abandoning the effort. 
The control panel does not call RPS again until it 
downloads the log and the Log % Full percentage is 
reached. These events are also sent to the control 
panel’s event log and to the local printer(s) if 
installed. 
 
The Log Overflow Event is not sent to 
the central station unless Expanded 
Test Rpt
 is programmed Yes
Remote Program Dialing Exception: When an RPS 
phone number is programmed, the user can call RPS 
by entering [COMMAND][4][3] and pressing the 
[NEXT] key until CALLRPS? is displayed. Press 
[ENTER]. Only one attempt is made to contact RPS. 
 
 
Failure to program the RPS telephone 
number results in a BAD CALL TO RPS 
trouble event sent to the central station 
 
when the log threshold is reached. Refer 
 
RPS Passcode 
to the 
 prompt on page 35 for 
information about programming the RPS 
Default: 
999999 
telephone number. 
Selection:  0 to 9, A to F  
(six characters required) 
Enter six characters. Do not use a space in the 
passcode. 
The control panel verifies the remote programming 
software at the central station has valid access 
before connecting using the RPS passcode.