D9412GV2/D7412GV2 | Program Entry Guide | 2.0  GV2MAIN 
EN | 81 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
 
A# Duress Relay 
Default: 
Blank 
Selection: 
Blank, 1 to 128 (1 to 64 for 
D7412GV2), A, B, or C 
Activates when a Duress alarm is generated from a 
keypad assigned to the specified area. 
 
 
Burg Time needs a bell period 
programmed and A# Duress Enable 
must be Yes. This relay activates when 
the Burg Bell starts and deactivates when 
the Burg Bell time ends. The Burg Bell 
pattern has no effect on this relay 
function. 
A# Perim Fault 
Default: 
Blank 
Selection: 
Blank, 1 to 128 (1 to 64 for 
D7412GV2), A, B, or C 
Activates when a Controlled Perimeter point (P## 
Type 1
) assigned to the specified area is faulted,  
regardless of the armed state of the area. This relay 
provides a steady output until all Perimeter points in 
the area return to normal. 
 
 
This relay does not activate on interior 
faults. To detect all area point faults, 
program all points as Perimeter points in 
the area where this relay is assigned. 
A# Silent Alarm 
Default: 
Blank 
Selection: 
Blank, 1 to 128 (1 to 64 for 
D7412GV2), A, B, or C 
This relay activates when a point assigned to the 
specified area and programmed for P## Silent Bell 
goes into alarm. 
Alternate Functions for A# Silent Alarm 
• 
•  Area 5: Programming a non-zero value in the 
Silent Alarm Relay for Area 5 enables Ground 
Fault Detect
 on the D9412GV2 or D7412GV2 
Control Panel using firmware versions 7.01 and 
7.02 only. In version 7.03 and above, this setting 
is not used.  
Area 4: For time control, programming any value 
other than 60 in the Silent Alarm Relay for Area 4 
enables AC (traditional) time control. Entering a 
value of 60 for Area 4 disables AC time control 
and switches the time control to the on-board 
crystal. This alternate function is replaced by the 
CrystalTime Adj prompt (refer to page 142) in 
the GV2AUX handler for the D9412GV2 and 
D7412GV2 in firmware v7.07 and later.  
To meet UL 864 requirements, enable 
Ground Fault Detect
 
 
Refer to Ground Fault Detect in the 
D9412GV2/D7412GV2 Operation and Installation 
Guide
 (P/N: F01U003641). 
• 
• 
Area 7: Perimeter Armed Relay, when enabled, 
turns the Fail to Close Relay function into a 
Perimeter Armed Relay function. 
To change the Fail to Close Relay into a 
Perimeter Armed Relay function, program 63 in 
the Silent Alarm Relay for Area 7. Set A# Fail to 
Close Relay
 to the area to be Perimeter Armed. 
Refer to  Area 8 for additional information. This 
alternate function is replaced by the Perimeter 
Relay
 prompt (refer to page 142) in the GV2AUX 
handler for the D9412GV2 and D7412GV2 in 
firmware v7.07 and later. 
Area 8: Programming a value of 64 in the Silent 
Alarm Relay for Area 8 causes the Area Armed or 
Perimeter Armed Relay (refer to Area 7) to 
activate at the beginning of the exit delay time. 
This alternate function is replaced by the 
EarlyArmed Relay prompt (refer to page 142) in 
the GV2AUX handler for the D9412GV2 and 
D7412GV2 in firmware v7.07 and later. 
2.13.2 Panel-Wide Relays 
The following eleven relay options activate when they 
occur anywhere in the control panel. They are not 
restricted by area boundaries. 
AC Failure 
Default: 
Blank 
Blank, 1 to 128 (1 to 64 for 
Selection: 
D7412GV2), A, B, or C 
Activates when the control panel responds to an AC 
power failure as programmed in AC Fail Time in 
Section 2.5 Power Supervision on page 28. This relay 
automatically resets when AC power restores. 
Use this relay to create audible 
annunciation. Enable the keypad’s 
trouble sounders for all applications 
 
except commercial fire systems.