D9412GV2/D7412GV2 | Program Entry Guide | 2.0  GV2MAIN 
EN | 82 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
 
Battery Trouble 
Summary Fire 
Default: 
Blank 
Default: 
Blank 
Selection: 
Blank, 1 to 128 (1 to 64 for 
D7412GV2), A, B, or C 
Selection
Blank, 1 to 128 (1 to 64 for 
Activates when battery voltage falls below 85% of 
capacity (12.1 VDC) for a fully charged (13.8 VDC) 
battery, or when the battery is in a missing condition. 
This relay automatically resets when battery power 
restores. 
 
 
Use this relay to create audible 
annunciation. Enable the keypad’s 
trouble sounders for all applications 
except commercial fire systems. 
Phone Fail 
Default: 
Blank 
Selection: 
Blank, 1 to 128 (1 to 64 for 
D7412GV2), A, B, or C 
Activates when a telephone line failure occurs. A time 
must be entered in Ph Supv Time (refer to Section 2.2 
Phone Parameters
 on page 12) for this relay to 
activate. This relay resets automatically when restoral 
of the phone line(s) occurs. 
Comm Fail 
Default: 
Blank 
Selection:  Blank, 1 to 128 (1 to 64 for 
D7412GV2), A, B, or C 
Activates when a control panel cannot communicate a 
report after making ten attempts to each routing 
destination. At the same time, COMM FAIL RT ## 
displays at the keypad. This relay automatically resets 
when a report is sent successfully. 
 
 
Use this relay to report primary digital 
report failure to an alternate 
communication device. 
 
 
Log % Full 
Default: 
Blank 
Selection: 
Blank, 1 to 128 (1 to 64 for 
D7412GV2), A, B, or C 
Enter the number of the relay that activates when the 
log reaches the programmed percentage of its 
capacity as programmed in the Log % Full prompt 
under GV2MAIN. This relay provides a steady output 
until a Get Log and Set Pointer is executed from the 
remote programming software (RPS). 
D7412GV2), A, B, or C 
Enter the number of the relay that activates when any 
Fire point in the system (P## Type 0P## Fire Yes
enters into alarm. This relay provides a steady output 
until all Fire points in the system return to normal. 
Refer to 
 on page 139
 for 
details on alternate operation. 
Summary Alarm 
Default: 
Blank 
Blank, 1 to 128 (1 to 64 for 
Selection: 
D7412GV2), A, B, or C 
Enter the number of the relay that activates when a 
Non-fire point enters into alarm. This relay provides a 
steady output until the alarm is acknowledged by a 
valid pass code, then cleared from alarm memory with 
an acknowledgment at the keypad. 
This relay does not activate for silent and 
invisible alarms. 
 
Summary Fire Tbl 
Default: 
Blank 
Blank, 1 to 128 (1 to 64 for 
Selection: 
D7412GV2), A, B, or C 
Activates when any Fire point in the control panel is in 
trouble, or if a Fire Supervision point is missing. This 
relay provides a steady output until all Fire points 
restore to a normal condition.  
Summary SupFire 
Default: 
Blank 
Blank, 1 to 128 (1 to 64 for 
Selection: 
D7412GV2), A, B, or C 
Activates when any Fire Supervisory point in the 
control panel is in a supervisory condition (off-
normal). This relay provides a steady output until all 
Fire Supervisory points are restored to a normal 
condition.