5. INSTALLATION NOTE:  Do not install batteries until verifying that the cabinet 
mounting hardware is secure. Failure to do so may result in the cabinet flipping 
over, causing severe injury to the installer. 
 
6. 
Install the power supply and batteries in the cabinet as outlined in this manual.
 
 
 
Section 4:   Front Panel Controls, Connections and Indicators 
 
The front panel of the power supply contains various connectors, indicators and all operator 
controls.   These items are described as follows. 
 
Controls 
 
Circuit Breakers:
  Input and output circuit breakers are described as follows: 
 
a)  Output Circuit Breaker:  This 20-amp circuit breaker, located at the left side of the 
front panel, protects the power supply in case a fault condition occurs on the output 
circuit.  This circuit breaker is a push-to-reset device. 
 
b)  Battery Circuit Breaker:  80 amp circuit breaker protects battery circuit and input 
wiring.  This circuit breaker is also used as a DC switch to apply and remove battery 
power to the power supply. 
 
 
Switches:  One pushbutton switch controls functions within the power supply: 
 
TEST Switch:  This switch, located below the indicator LEDs on the front panel of the 
inverter module, initiates and cancels local battery test. 
 
Connections: 
 
Output Connectors: 
 
The Blackhawk Series power supplies contain one power output connector, located in 
the lower left corner of the front panel.  The mating Anderson mini-power pole 
connector provides the means for connecting output power to the appropriate network 
power connector in the cabinet.  The black connector is hot; the white connector is 
ground return for the output. 
 
BATTERY: Anderson-type connector: used for connecting the external battery to the 
power supply. 
 
BATTERY TEMP SENSOR:  Mini Mate-N-Lok: connects the external temperature 
probe for temperature compensated battery charging. 
 
 
14