BLACKHAWK! Power Supply Blackhawk Series Broadband Power Supplies Benutzerhandbuch

Seite von 31
CABINET INDICATORS:  Mini Mate-N-Lok: connects the enclosure alarm and status 
lamps to the power supply for external status indication.  The power supply will activate 
an external green lamp to indicate normal operation or will activate a red alarm lamp to 
indicate battery operation or a failure condition in need of correction. 
 
 
Indicators: 
 
A  group of light emitting diodes (LEDs) on the front of the inverter module provides visual 
indication of power supply operational status.  These LEDs are described as follows: 
 
Power Supply Status Indicators:  The LEDs on the inverter module front panel form the 
Status At A Glance display that indicates operational status of the power supply circuits.  
Under normal operating conditions with line power applied and the battery fully charged, all 
LEDs with the exception of the TEST indicator should illuminate green.  Any alarm or 
abnormal operating condition will result in one or more LEDs illuminating either amber or 
red. 
 
Any indicator of a color other than green will be easily noticed so operating or service 
technicians will be able to discern, at a glance, the operational status of the power supply.  
Indicators and their operational states are described as follows: 
 
LINE:   AC input LED indicates one of three status conditions: 
o
  Green:  line power available and within acceptable limits 
o
  Amber:  qualifying line following restoration 
o
  Red:  line power low in voltage or completely failed 
 
BATTERY:  Battery LED indicates one of three states: 
o
  Green:  Battery fully charged, voltage normal 
o
  Amber:  Battery charger is operating in the high rate mode 
o
  Red:  Alarm; battery is discharging or low battery cutoff point attained 
 
SENSOR:  This LED indicates status of the temperature probe: 
o
  Green:  Probe connected and operating normally 
o
  Not illuminated: Alarm; probe has become disconnected or has failed 
 
TEST:  This indicator operates in conjunction with the remote/local battery test function.  
Testing may be initiated locally by actuating the TEST switch or remotely by issuing 
appropriate commands via the status monitor port.  This LED indicates  the 
following operational states: 
o
  Green:  Testing locally by actuating the TEST switch 
o
  Amber:  Flashes when serial data is being sent to the transponder 
o
  Red:  Alarm; check battery for state-of-charge or failure condition 
 
 
 