Utica Boilers UB95M-200 Installationsanweisungen

Seite von 28
7
Startup
1. 
Start boiler after completing all instructions in 
Installation, Operation and Maintenance Manual.
2. 
Start boiler by turning thermostat up to call for heat.
3. 
Once boiler has started and is operating, continue 
startup procedure by performing all following steps to 
set and verify operation of controls.
Set Space Heating Operation
1. 
Verify Space Heating Mode
A.  Press “Mode” button until display shows [PARA]. 
This is parameter mode.
B.  Press “Step” button until first digit of display shows 
“3.”
C.  Last digit must show “1.” If any other number 
displays, press “+” button until “1” shows in right-
hand digit, then press “Store” button to save this 
setting.
2. 
Set space heating target temperature
A.  Press “Step” button until first digit of display 
shows “4.” Last three digits show outlet water 
temperature setting.
B.  Press “+” or “-” buttons to change setting to 
desired outlet water temperature. Factory default 
setting is 180°F.
• Outdoor sensor installed: Setting is target 
temperature for outdoor temperature at or 
below factory setting (32°F). At higher outside 
temperatures, control module calculates target 
temperature.
• When summer/winter switch is used, closing 
switch will disable boiler (space heating) circulator 
during summer operation.
• Outdoor sensor not installed: Setting is target 
temperature at all times.
C.  Press “Store” button to save setting.
Check DHW Operation Setup
If control is already in parameter mode , skip step 1 (below) 
and proceed to step 2.
1. 
Press “Mode” button until display shows  [PARA] 
(parameter mode).  
2. 
Press “Step” button until first digit of display shows “2.”
3. 
Last digit must show “1.” If another number displays, 
press “+” button until “1” shows in right-hand digit, 
press “Store” button to save this setting.
4. 
Control module turns on DHW circulator when indirect 
water heater operating control closes. Control module 
shuts off boiler circulator (stops space heating) during 
calls for DHW heating. 
Verify Operation – Space Heating
Information below presented in brackets “[ ]” represents 
actual boiler control panel display with first digit indicating 
boiler status and last three digits showing measured boiler 
water temperature. (Ex.- [A180] indicates status of “A” and 
boiler water temperature of 180°F.)
1. 
Turn down DHW aquastat on DHW tank (if used). If 
necessary, turn off power and remove one of DHW 
aquastat wires to ensure boiler will not receive DHW 
heat call.
2. 
Turn off power to boiler at service switch.
3. 
Wait few seconds, then turn on power to boiler.
• [180] Self-check on power-up for a few seconds.
• [0180]  No call for heat.
4. 
Raise room thermostat to call for heat.
• [5180] Blower/boiler circulator on. Blower and boiler 
circulator energize and control checks for air flow.
• [1180] Pre-purge. Blower speed will increase to ignition 
speed. Blower will run in pre-purge for 10 seconds.
• [2180] Ignition. After pre-purge, control module opens 
gas valve and starts ignition spark.
• If burner flame proves within 4.5 seconds, burner 
continues to fire. Burner will fire at startup rate for 
about 10 seconds to allow flame to stabilize.
• If burner flame does not prove within 4.5 seconds, 
control module attempts ignition sequence again. 
Flame must prove within 6 attempts or control will 
lockout (display will show [E 02]).
• Verify flame failure operation by closing boiler manual 
gas cock to prevent gas flow. Open manual gas valve 
after testing.
• [3180] Burner on, space heating. Once flame is 
proven and stable, burner turns down to low fire for 
approximately 2 minutes.
• After this low fire period, burner is allowed to modulate. 
Firing rate depends on actual outlet water temperature 
versus target temperature.
5. 
Allow boiler to bring water temperature to target 
temperature.
• [6180] Target temperature reached. Burner shuts 
down. Blower runs in post-purge (see below), then 
turns off. Boiler circulator continues to run as long as 
there is call for heat.
6. 
Lower room thermostat to stop call for heat.
NOTICE
Instructions in this manual are based on factory 
default parameter settings.
5 - BOILER STARTUP