PROGRAMMING THE BOILER CONTROL MODULE
IMPORTANT: The factory default setting for opera-
tion of the boiler control module is for thermostat con-
trol. The module must be programmed, as described 
in the following, to operate from a 0-10vdc input sig-
nal to operate correctly with the AM4 module.
Follow  instructions  in  the  “Installation  Manual”  (P/N# 
240006103) and the “Control Manual and Installation 
Instructions”  (P/N#  240006104)  to  install,  set  up  and 
adjust the boiler.
DIFFERENCES FROM STANDARD OPERATION
1.  The  HAM  module  responds  to  a  signal  from  the 
multiple  boiler  controller.  The  boiler  will  not  cycle  on 
thermostat  action,  but  on  the  control  signal  from  the 
HAM module to the boiler control module. To test boiler 
operation, you will need to operate the multiple boiler 
controller to signal the boiler to initiate a call for heat to 
test the boiler and controls.
2. Parameter readouts (Boiler Control Module):
•  Parameter  4  will  not  show  outside  temperature. 
The boiler control module does not use an outside 
sensor when using the HAM module.
• Parameter 6 will not show target outlet water tem-
perature.  Water  temperature  control  is  performed 
by the multiple boiler controller.
PROGRAMMING THE CONTROL MODULE
FOR HAM INPUT
1. You must program the boiler control module to ac-
cept the 0-10 vdc input signal from the HAM module as 
described on the next page.
WARNING
Do  not  attempt  to  revise  any  other  control  set-
tings except those covered in the Boiler Control 
Manual  (P/N#  240006104)  and  Parameter  Guide 
(P/N# 240006105). Perform only the revisions de-
scribed in this document and the aforementioned 
manuals. Failure to comply could result in erratic 
or unreliable operation of the boiler.
2. Once the instructions for preparation of the boiler are 
completed,  activate  code  mode  on  the  boiler  control 
module as follows:
a. Press and hold the “Step” button. Continue hold-
ing “Step” and press “Mode” as well. Hold both but-
tons for 2 seconds or longer. The module readout 
will  change  to  [CODE].  Release  the  “Step”  and 
“Mode” buttons.
b. Press “Step” once. The module readout will show 
[C - XX], where the “XX” will be a random number.
c. Use “+” or “-” to change the last two digits until the 
display shows [C - 05].
NOTE: To change numbers one unit at a time, tap the “+” or “-” 
buttons. To make the number change quickly, hold down “+” or 
“-” buttons.
d. When the display shows “C - 05”, press “Store” to 
enter the code number.
3. Revise parameter 34 as follows:
a. Once the code has been stored, change to the 
“Parameter”  mode  by  pressing  the  “Mode”  button 
until parameter mode is selected.
b. Press repeatedly until the readout shows [P . 34]. 
The readout sequence as you press the button will be:
[1 140], [2 .01], [3 .01], [4 190], [P . 05], [P . 06],
[P . 07], etc.
The  readout  will  continue  to  show  “P  .  ”  followed 
by a two digit number that increases each time you 
press the “Step” button.
NOTE: The actual parameter values displayed may vary, de-
pending  on  the  application.  The  parameter  sequence  will  al-
ways occur in the order shown.
c. When the readout shows [P . 34], stop pushing 
the “Step” button. Wait a few seconds and the dis-
play will show the current setting for parameter 34 in 
the right two display spaces.
d. Press the “+” or “-” buttons to change the value 
until the display shows [- - 04].
e. Save the change by pressing the “Store” button.