Utica Boilers SSC Handbuch

Seite von 6
P/N 240010478 REV B, [06/2014]
Engineer:____________________________________________
Project Name:________________________________________
Project Location:______________________________________
Contractor:___________________________________________
2201 Dwyer Ave.    Utica, NY 13501     www.UticaBoilers.com
APPLICATION: 
Gas fired hot water heating boiler for indoor installations.  Approved for closet or alcove installations.  For 
use with natural or liquefied petroleum gases (LP/propane) LP conversion kit provided with the boiler.  Wall 
mounted, optional floor mount kit available.  Constructed and hydrostatically tested for maximum allowable 
working pressure of 150 PSIG (pounds per square inch gauge) in accordance with ASME boiler and pressure 
vessel code, section IV, rules for construction of heating boilers.
BOILERS INCLUDE:
• Wall Mount Bracket
• Boiler Control Module
 
X
Line voltage/intermittent direct spark ignition.  Replaceable fuse /extra spare fuse shipped with the 
control.
 
X
Controlling premix modulating gas valve and blower.
 
X
User interface with LCD screen display English text—boiler status indication.  
 
X
Function Programming Keys  - Reset, Menu, Enter and arrow s  (+  - ).
 
X
Central Heating CH  and Domestic Hot Water DHW setpoints.  Domestic hot water priority with 
programmable maximum priority time.
 
X
 Outdoor air sensor.  Programmable reset curves and warm weather shutdown or fixed water 
temperature operation. 
 
X
Boost function temperature setting and adjustable boost time .
 
X
Integral multiple boiler control capability up to 15 boilers.  Requires an optional system sensor 
 
X
Service reminder status.
• Boiler Combustion System
 
X
 Premix Gas valve and blower assembly with 20-100% modulating firing rate.  Turn down ratio (5:1)  gas input. 
 
X
 Stainless Steel Fiber Mesh Burner 
 
X
 Flame Sensor