Utica Boilers SSC Handbuch

Seite von 6
P/N 240010478 REV B, [06/2014]
Models & Capacities
Size
Boiler Input Rate (MBH)
(1)
Heating 
Capacity (MBH)
(1)(2)
Net AHRI
 Rating, Water 
(MBH)
(1)(3)
AFUE
(2)
Maximum
Minimum
UBSSC-050
50
10
46
40
95.0
UBSSC-075
75
15
69
60
95.0
UBSSC-100
100
20
91
79
95.0
UBSSC-150
150
30
139
121
95.0
UBSSC-200
200
40
185
161
95.0
UBSSC-299
299
60
273
239
95.0
* The UBSSC Models are ENERGY STAR rated products.
(1)
 1000 Btu/hr (British Thermal Units Per Hour)
(2)
 Heating Capacity and AFUE (Annual Fuel Utilization Efficiency) are based on DOE (Department of Energy) test 
procedures. 
(3) 
Net AHRI Ratings based on piping and pickup allowance of 1.15. Contact Technical Support before selecting boiler for installations 
having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems,  etc.
• UL listed probe type low water cutoff with status indicator lights and test feature.
• Heat Exchanger Assembly
 
X
Vertically mounted single piece helical fin tube coil.  Manufactured out of 316L stainless steel tubing 
with 444 stainless steel fins welded onto the coil with a laser automated process.  ASME stamped  with 
a 150 psi maximum allowable  working pressure.  A 30psi safety relief valve is standard. 
 
X
Built-in Primary/Secondary manifold and piping system and heat exchanger pump.  
 
X
Non-metallic flue gas collector with built in condensate drain trap .
• Electrical
 
X
Removable low voltage terminal strip. 
 
X
Line voltage junction box with DWH Pump and CH Pump connections.  
OPTIONAL EQUIPMENT:
• Floor mounting stand
• Multiple boiler system sensor
2201 Dwyer Ave.    Utica, NY 13501     www.UticaBoilers.com