Omron CompoBus/D (DeviceNet) Communications Card 3G3FV-PDRT1-SIN Benutzerhandbuch

Seite von 161
3-4
3-1-4 Baud Rate and Node Address Settings
In a CompoBus/D Network, the baud rate can be set to 500 Kbps, 250 Kbps, or 125 Kbps. To manage
Master/Slave communications, numbers are assigned as node addresses.
Baud rate setting pins
Node address setting pins
Note
Default settings are all OFF.
H
Baud Rate Setting Pins
Pin
500 Kbps
250 Kbps
125 Kbps
DR1
ON
OFF
OFF
DR0
OFF
ON
OFF
H
Node Address Setting Pins
Pin
Node Address
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
to
63
ADR5
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
to
ON
ADR4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
to
ON
ADR3
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
to
ON
ADR2
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
to
ON
ADR1
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
to
ON
ADR0
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
to
ON
Note 1. The same node address cannot be used for more than one Slave connected to the commu-
nications line.
Note 2. Remote I/O allocations in the CPU Unit are affected by the node addresses, so make sure that
the remote I/O allocations do not overlap before setting a node address. Refer to Chapter 4
CompoBus/D System Startup
.
Setup and Wiring
Chapter 3