Omron CompoBus/D (DeviceNet) Communications Card 3G3FV-PDRT1-SIN Benutzerhandbuch
4-15
4-2-4 Frequency Reference Settings and Display Units
The parameters for units of frequency (speed) data used in CompoBus/D communications are set with
the following constant. The standard unit used with DeviceNet is r/min, so always set the number of
motor poles.
the following constant. The standard unit used with DeviceNet is r/min, so always set the number of
motor poles.
Default setting: 0
Constant
Content
o1-03
0
0.01 Hz
1
0.01% (max. frequency is 100 %)
2 to 39
r/min (Set the number of motor poles.)
40 to 39,999
Specifies the value used to set and display the maximum frequency.
jjjjj
Example: To display the maximum frequency as “200.0” specify “12000.”
Set a 4-digit value without the decimal point.
Set the position of the digit where the decimal point is to be displayed
starting from the rightmost digit.
starting from the rightmost digit.
CompoBus/D System Startup
Chapter 4