Omron CompoBus/D (DeviceNet) Communications Card 3G3FV-PDRT1-SIN Benutzerhandbuch

Seite von 161
5-5
Note 2. Control From Net shows the input status of word n, bit 5 (Net Control) for CompoBus/D com-
munications.
Note 3. The Reference From Net and Control From Net functions are applicable for Inverter software
versions S1042 and later. Check the version with the Inverter monitor function U1–14.
Note 4. Reverse Operation indicates reverse output status. This bit does not turn ON for DC braking
(DC injection).
Note 5. Forward Operation indicates either forward run status or DC braking (DC injection) status.
This bit turns ON even for DC braking (DC injection) during reverse run.
D
Rotational Speed Reference Data
Word address
n+1
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Signal name
Rotational speed reference data
Content
Communications data = Rotational speed reference x 2
a
a: Speed scale value of Class 2A, Instance 01, Attribute 16 (Initial value: 0)
The speed scale is assigned to the message function. For instructions on how to change it, refer to 5-2 Mes-
sage Communications.
The unit for the rotational speed reference is set in o1–03 (frequency reference setting and display units)
Setting example (providing reference of 1,800 r/min):
When the speed scale value is “0” and the number of motor poles is set in 01–03 (so unit is r/min):
1,800 r/min 
 1,800 x2
0
 
 1,800 
 0708 Hex
Note 1. Under the DeviceNet protocol, the unit for the speed reference is fixed as r/min. The number
of motor poles (2 to 32) must be set in parameter o1–03 (frequency reference setting and dis-
play units) when using DeviceNet (open network).
Note 2. If the setting in not within the proper range, the previous data will be retained and the desig-
nated rotational speed will not be entered.
D
Rotational Speed Monitor Data
Word address
m+1
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Signal name
Rotational speed monitor data
Content
Communications data = Rotational speed monitor x 2
a
a: Speed scale value of Class 2A, Instance 01, Attribute 16 (Initial value: 0)
The speed scale is assigned to the message function. For instructions on how to change it, refer to 5-2 Mes-
sage Communications.
The unit for the rotational speed monitor is set in o1–03 (frequency reference setting and display units)
Data conversion example:
When the speed scale value is “0” and the number of motor poles is set in 01–03, and the read data is 03E8
Hex:
03E8 Hex 
 1,000 
 1,000/2
0
 
 1,000 r/min
Note Under the DeviceNet protocol, the unit for the speed reference is fixed as r/min. The number of
motor poles (2 to 32) must be set in parameter o1–03 (frequency reference setting and display
units) when using DeviceNet (open network).
CompoBus/D Communications Card Operations
Chapter 5