Maytag PGC2MQ iQ Drive | Maytag M1200 97% AFUE Modulating Gas Furnace Technisches Handbuch

Seite von 8
7
ACCESSORIES
All models are 115 V, 60 HZ. Gas connections are 1/2" N.P.T. 
AFUE= Annual Fuel Utilization Efficiency 
PGC2MQ KITS
Description
SKU
2" Concentric vent kit
904177
3" Concentric vent kit
904176
2" Side wall vent kit
904617
3" Side wall vent kit
904347
U.S. LP Conversion kit (0 to 10,000 ft.) for US and Canada
904950
Bottom return filter 20 per box, "B" cabinet
904916
Bottom return filter 20 per box, "C" cabinet
904917
Bottom return filter 20 per box, "D" cabinet
904918
Side return filter kit
541036
Neutralizer kit
902377
Outdoor Sensor for conventional heatpump
920938
FURNACE 
MODELS
(BTU)
FURNACE 
INSTALLATION
SINGLE VENT PIPE LENGTH (FT.)
with 1 long radius elbow*
DUAL VENT PIPE LENGTH (ft.) 
with 1 long radius elbow on each pipe*
OUTLET
2” Diameter
OUTLET
3” Diameter
INLET/OUTLET
2” Diameter 
INLET/OUTLET
3” Diameter
60,000
Upflow
50
80
50
80
Horizontal
40
80
40
80
80,000
Upflow
60
90
60
90
Horizontal
50
90
50
90
100,000
Upflow
50
90
50
90
Horizontal
40
90
40
90
120,000
Upflow
N/A
90
N/A
90
Horizontal
N/A
70
N/A
70
*NOTES:
1 Subtract 2.5 ft. for each additional 2 inch long radius elbow, 5 ft. for each additional 2 inch short radius elbow, 3.5 ft. for each additional 3 inch 
long radius elbow, and 7 ft. for each additional 3 inch short radius elbow. Two 45
°
 elbows are equivalent to one 90
°
 elbow. 
2. Subtract 5ft for each 2” tee and 8ft for each 3” tee.
3. This table applies for elevations from sea level to 2,000 ft. For higher elevations, decrease pipe lengths by 8% per 1,000 ft of altitude.
4. The minimum length for 2” or 3” diameter vent pipe is 5 ft.
MAXIMUM PIPE LENGTH