MAKE ELECTRICAL CONNECTION - U.S.A. ONLY (EFFECTUER LE 
RACCORDEMENT ÉLECTRIQUE – ÉTATS-UNIS SEULEMENT)
Power Supply Cord
ELECTRICAL CONNECTION OPTIONS
1.
 
Choose electrical connection type
Power supply cord 4-wire receptacle
(NEMA Type 14-30R): Go to steps 1-2 
on page 12 for power supply cord strain 
relief: then steps 3-6 for 4-wire Power 
Supply Cord Connection section. Then, 
go to Venting Requirements.
3-wire direct connection: Go to steps 
1-2 on page 15 for direct wire strain relief: 
then steps 3-7 for 3-wire Direct Wire 
Connection section. Then go to Venting 
Requirements.
4-wire direct connection: Go to steps 
1-2 on page 14 for direct wire strain relief: 
then steps 3-8 for 4-wire Direct Wire 
Connection section. Then go to Venting 
Requirements. 
Power supply cord 3-wire receptacle
(NEMA Type 10-30R): Go to steps 1-2 
on page 13 for power supply cord strain 
relief: then steps 3-5 for 3-wire Power 
Supply Cord Connection section. Then  
go to Venting Requirements.
NOTE:
 If local codes do not permit connection of a 
cabinet-ground conductor to neutral wire, go to “Optional 
3-wire Connection” section. This connection may be 
used with either a power supply cord or a direct wire 
connection.
Direct Wire
A
B
C
C
E
F
D
2.
 
Remove terminal block cover
Before you start, disconnect power. Remove hold-down 
screw (D) and terminal block cover (A).
A. Terminal block cover 
B. External ground conductor screw
C. Center terminal block screw
D. Hold-down screw 
E. Neutral ground wire
F. Hole below terminal block cover