pressure. The regulator used on this unit will 
withstand a maximum input pressure of 1/2 psi, 
(12" WC). If the incoming line pressure is 
higher than this maximum rating, a step-down 
regulator is required upstream of the unit's 
factory-installed regulator. 
 
  The appliance and its individual shut-off valve 
must be disconnected from the gas supply 
piping system during any pressure testing of 
the homes’ gas line system at pressures in 
excess of 1/2 psig, (3.5kPa). 
 
  The appliance must be isolated from the gas 
supply piping system by closing its individual 
shut-off valve during any testing of the homes’ 
gas system at pressures equal to or less than 1/2 
psig, (3.5kPa). 
 
3. Rigid connections:  Incoming gas is brought 
from the inlet pipe at the rear of the unit to the 
pressure regulator, then through the upper 
manifold for distribution. The only connection 
necessary is from the service line, through the 
installer-supplied shut-off valve, to this inlet 
pipe. 
 
  Be sure to double check any installer-supplied 
pipes and fittings, and/or blow compressed air 
through them to clean out dirt particles, 
threading chips, or other foreign matter before 
connecting the unit to the service line. Such 
particles will clog orifices when gas pressure is 
applied.  Service to clean such clogs is not 
covered by the warranty.
 
 
  Check all gas connections for leaks using a 
soapy solution before lighting any pilots. DO 
NOT USE AN OPEN FLAME TO CHECK 
FOR LEAKS! 
Using an open flame to check a 
new connection is not only dangerous, but it 
will also miss small leaks that a soapy solution 
would detect. 
 
4. Flexible connections:  If the unit is to be 
installed with flexible couplings and/or a 
"quick-disconnect," the installer must use a 
commercially approved AGA Design Certified 
flexible connector of at least 1/2" NPT, in 
compliance with ANSI Z21.41.  
 
  In Canada, a connector complying with CAN 
16.10 - 88, and a quick disconnect device 
complying with CAN 16.19M - 79 must be 
installed with a strain relief device to guard 
against the transmission of strain to the 
connector. 
 
5.Air shutter adjustments are the responsibility of 
the installer, and are not covered by warranty. 
Burners are preset at the factory and may need 
fine-tuning by the installer. 
 
 
 
 
GAS CONVERSION 
 
Any field gas conversions will automatically void the manufacturers warranty!!    Gas conversions 
should only be performed by a licensed professional to assure a complete and safe conversion.  Please 
contact your distributor for additional information regarding gas conversion. 
 
WARNING
IN ORDER TO AVOID A FIRE OR EXPLOSION, CAUSING PROPERTY DAMAGE, PERSONAL 
INJURY OR DEATH; PRECAUTION MUST BE TAKEN WHEN PERFORMING A CONVERSION BY ENSURING 
THAT THE VALUES IN THE GAS PRESSURE CHARTS ARE EMPLOYED WHERE APPLICABLE. 
 
For additional information regarding field conversions, contact your distributor/dealer.