Honeywell R0512 Benutzerhandbuch

Seite von 86
EXCEL 50/100/500/600/800 
ATTRIBUTES 
 
 
EN2B-0092GE51 R0512 
25 
possible that not every value is displayed when high frequency values with high 
scaling factors are received. 
 
 
Resetting the interval count 
Resetting takes place either manually via an operating unit, by reaching the 
“Interval Limit” value, or by reaching the “totalized” constant, which is 2 to the power 
of 31. 
 
 
Totalizer overflow 
When the “Interval Limit” or the “totalized” constant is reached, a “Totalizer 
Overflow” system alarm is created. 
 
 
Interval Limit 
The attribute “Interval Limit” is that value of the "Interval Count" attribute which, 
when reached, will generate a “Totalizer Overflow” alarm. The highest possible 
value for the attribute "Interval Count" is 99,999,999. 
 
 
Electrical energy example 
A message should be generated after the “consumption” of 5 MWh of electrical 
power. The input in the attribute “Interval Limit” must therefore be 5 MWh. 
Once the interval count reaches its reporting level of 5 MWh, then a report is 
generated, the interval count is reset to “Zero”, and a new totalizing period is 
started. 
 
 
I/O Characteristic 
The attribute "I/O Characteristic" enables the user to display special input and out-
put characteristics (see Fig. 13) for analog inputs/outputs. Special characteristics 
permit, for instance, the adaptation of Excel 50/100/500/600/800 to many different 
sensor types. Ten individual input/output characteristics are available per 
Excel 50/100/500/600/800 controller. 
Each special characteristic is assigned a name that can be recalled from the 
attribute "I/O Characteristic". Thus, the desired characteristic can be assigned to 
the selected datapoint. 
 
Fig. 13. Example of a special output characteristic 
Creation of characteristics is carried out at programming level. Up to a maximum of 
four reference points can be specified per characteristic. Up to ten different 
characteristics can be defined for each controller. 
For XFL and XFC I/O modules, user-defined characteristics are supported from 
CARE 5.0 and controller firmware 2.06.05 onwards. 
 
 CAUTION 
Regarding I/O characteristic, the behavior of controllers with OS < 2.06.05 
engineered using CARE 4 differs significantly from controllers with OS 
2.06.05 and higher engineered using CARE 7 and higher. See also section 
“Controller OS 2.06 usage and functionality in CARE 4 and CARE – XL500 
7.01.02” in Excel CARE – User Guide (EN2B-0182GE51).