EXCEL 50/100/500/600/800 
ATTRIBUTES 
 
 
EN2B-0092GE51 R0512 
27 
In this way it is possible to determine the last switch-on point of a fan, pump, etc. 
connected via a digital output. 
 
In the case of analog inputs and pseudo analog points, the last time an alarm limit 
occurred is stored. 
 
 
LED Mode (XF823x, XFL823x, and XFx830x modules) 
The XF823x Panel Bus Binary Input Module, the XFL823x Lonworks Bus Binary 
Input Module, and the XF830x / XFU830x modules support the “LED Mode” 
attribute, which can be set in the CARE datapoint editor. The following attribute 
options are provided: 
 
•  “Alarm” 
LEDs will be red/green (red = alarm state, not XF830x /  
 
 
XFU830x modules) 
•  “Status” 
LEDs will be yellow/off (yellow = active state) 
 
NOTE:
 
XF830x / XFU830x modules do not support the Alarm option. Hence, do 
not assign this attribute to datapoints allocated to one of these modules. 
 
NOTE:
 
When the XFL823x L
ON
W
ORKS
 Bus Binary Input Module is used with 
non-Excel 800 controllers, the LED mode can only be set in the 
L
ON
W
ORKS
 NV settings in CARE, and not in the CARE datapoint editor. 
 
 
Maintenance Alarm 
 
Specifying a maintenance alarm 
In the case of those datapoints for which an hours run log has been activated, a 
time entry can occur within the attribute "Maintenance Alarm" to indicate after how 
many operational hours an alarm message should be generated. Entering “Zero” 
results in no alarm message. 
 
Example: 
 
Maintenance should be carried out every 500 hours on the heating circuit pump 
controlled via a digital output. To achieve this, a time interval duration of 500 hours 
is entered in the attribute "Maintenance Alarm" for this datapoint. At the same time, 
activation of the hours run log must also take place in the attribute “Hours Run log” 
for this datapoint. An alarm message now occurs after 500 hours, to bring to the 
operator’s attention the necessary pump maintenance. 
 
 
Manual Value 
When the attribute "Operating Mode" is set to "Manual", the operator can enter a 
manual value or state, and the application program will work with this manual value 
or state until the operating mode is set back to “Automatic”. 
 
 
Fig. 15. Example of a sensor input