Honeywell R0512 Benutzerhandbuch

Seite von 86
EXCEL 50/100/500/600/800 
ATTRIBUTES 
 
 
EN2B-0092GE51 R0512 
31 
**  Output only (V2.0.x) 
 
 
Digital points 
Table 14 indicates the digital point signals depending on the attribute "Operating 
Mode": 
 
Table 14. Digital point signals 
 
 
auto operating 
mode 
manual operating 
mode 
remote** 
operating mode 
automatic value* 
ON 
don’t care 
don’t care 
manual Value 
don’t care 
OFF 
don’t care 
remote value 
n/a 
n/a 
ON 
resulting Value 
ON 
OFF 
ON 
output signal 
HIGH 
LOW 
HIGH 
*Automatic value is either the physical point value (inputs) of the value from the 
program (outputs) 
**Output only (V2.0.x) 
 
 
Alarming 
The change from the 'automatic' to the 'manual' mode will create a point alarm if 
other alarm conditions are set accordingly. 
 
 
Firmware prior to V.2.04.x 
With controller firmware prior to V.2.04.xx, the alarm will report the status of the 
operating mode as it was before the change. 
 
 
Firmware V.2.04.x 
Beginning with controller firmware V.2.04.x, the alarm will report the status of the 
operating mode as it is after the change. 
 
 
Output Type 
Three-position outputs are digital outputs. From an operational viewpoint, they are 
assigned the same datapoint description as analog outputs, i.e. a three-position 
output possesses attributes similar to those of an analog output. 
 
 
Analog or 3-position output 
The attribute "Output Type" determines whether the analog output datapoint 
description should be assigned to an analog output or to a three-position output. 
The following inputs are possible: 
 
•  Continuous 
 
The analog output datapoint description is assigned to 
 
 
 
an analog output. 
•  Three-position   
The analog output datapoint description is assigned to  
 
 
 
a three-position output. 
•  Remote three-position  Output to the Excel 100 MCE 3 and MCD 3 output 
 
 
 
modules. 
 
 
Subtype 
The attribute "Subtype" is used in conjunction with digital outputs and flexible 
datapoints. It determines whether the digital output is of the non-pulsed type. 
 
 
Point Alarms 
The attribute "Point in Alarm" refers to alarm messages from the alarm attributes 
"Min. Limit", "Max. Limit", and "Alarm Status". 
The attribute "Point in Alarm" indicates whether or not those datapoints using these 
attributes are currently in alarm. 
The following entries are possible: 
 
•  Yes = the chosen datapoint is in alarm 
•   No = the chosen datapoint is not in alarm