ATTRIBUTES
EN2B-0092GE51 R0512
31
** Output only (V2.0.x)
Digital points
Table 14. Digital point signals
auto operating
mode
manual operating
mode
remote**
operating mode
automatic value*
ON
don’t care
don’t care
manual Value
don’t care
OFF
don’t care
remote value
n/a
n/a
ON
resulting Value
ON
OFF
ON
output signal
HIGH
LOW
HIGH
*Automatic value is either the physical point value (inputs) of the value from the
program (outputs)
**Output only (V2.0.x)
program (outputs)
**Output only (V2.0.x)
Alarming
The change from the 'automatic' to the 'manual' mode will create a point alarm if
other alarm conditions are set accordingly.
other alarm conditions are set accordingly.
Firmware prior to V.2.04.x
With controller firmware prior to V.2.04.xx, the alarm will report the status of the
operating mode as it was before the change.
operating mode as it was before the change.
Firmware V.2.04.x
Beginning with controller firmware V.2.04.x, the alarm will report the status of the
operating mode as it is after the change.
operating mode as it is after the change.
Output Type
Three-position outputs are digital outputs. From an operational viewpoint, they are
assigned the same datapoint description as analog outputs, i.e. a three-position
output possesses attributes similar to those of an analog output.
assigned the same datapoint description as analog outputs, i.e. a three-position
output possesses attributes similar to those of an analog output.
Analog or 3-position output
The attribute "Output Type" determines whether the analog output datapoint
description should be assigned to an analog output or to a three-position output.
The following inputs are possible:
• Continuous
description should be assigned to an analog output or to a three-position output.
The following inputs are possible:
• Continuous
The analog output datapoint description is assigned to
an analog output.
• Three-position
The analog output datapoint description is assigned to
a three-position output.
• Remote three-position Output to the Excel 100 MCE 3 and MCD 3 output
modules.
Subtype
The attribute "Subtype" is used in conjunction with digital outputs and flexible
datapoints. It determines whether the digital output is of the non-pulsed type.
datapoints. It determines whether the digital output is of the non-pulsed type.
Point Alarms
The attribute "Point in Alarm" refers to alarm messages from the alarm attributes
"Min. Limit", "Max. Limit", and "Alarm Status".
The attribute "Point in Alarm" indicates whether or not those datapoints using these
attributes are currently in alarm.
The following entries are possible:
• Yes = the chosen datapoint is in alarm
"Min. Limit", "Max. Limit", and "Alarm Status".
The attribute "Point in Alarm" indicates whether or not those datapoints using these
attributes are currently in alarm.
The following entries are possible:
• Yes = the chosen datapoint is in alarm
• No = the chosen datapoint is not in alarm