Sterling A0554831 Benutzerhandbuch

Seite von 70
2-40 HP Portable Chillers 
Chapter 7: Appendix 
57 of 70 
Remote Condenser Assembly Models 
 
 
To convert inches to cm, multiply dimension by 2.54. 
 
 Fan(s) 
d e f Remote 
Condenser 
Refrigeration 
g 
 Each 
Totals 
e f Overall 
Dimensions Connections 
Charge
HP Dia. 
Motor 
Amps 
 
Air 
flow 
Net 
wt. 
Length Width Height
Mtg. Discharge Liquid  R-22 
 in.  hp 
c  
460V 
Fans 
cfm 
lbs.‘A’(in.) ‘B’(in) ‘C’(in.) ‘D’(in) ODS(in.) ODS(in.) lbs. 
g
26 
3/4 hp 1 ø 
2.4 
6,450
260  49.8 43.0 40.5 40.0  11/
7/
3.6 
7.5 26 1/3 hp 3 ø 
3.7 2 
12,400
470 69.8 43.0 40.5 60.0  11/
7/
3.6 
10 26 1/3 hp 3 ø 
3.7 2 
13,700
510 89.8 43.0 40.5 80.0  13/8 11/
4.6 
15 26 1/3 hp 3 ø 
5.0 3 
20,500
550 
129.8 43.0  40.5 120.0
15/8 11/
6.4 
20 
30  1 1/2 hp 3 ø 
5.9 
23,000
840  125.0 45.5  50.0 108.0
15/8 15/
10.0 
25 
30  1 1/2 hp 3 ø 
5.9 
21,900
860  125.0 45.5  50.0 108.0
15/8 15/
16.0 
30 
30  1 1/2 hp 3 ø 
9.4 
34,800 1,280
180.0 45.5  50.0  i 
21/8 21/
24.0 
40 
30  1 1/2 hp 3 ø  12.9 
46,400 1,690
235.0 45.5  50.0  i 
21/8 21/
29.0 
c  ø  represents electrical phase; all motors are 1,140 rpm. Multiply hp by 0.746 to convert to kW
d  All first fan motors (Header Side) are ¾ hp (0.56 kW) single phase variable speed. 
e  Multiply 460V amperages by 2.0 for 208-230V amperages. 
f  Multiply 460 V amperages by 0.8 for 575 V amperages. 
g  Refrigeration charge is for remote condenser only! 
h  To convert cfm to cmh, multiply by 1.699. To convert lbs. to Kg, multiply by 0.454. 
i  See drawing above.