Sterling A0554831 用户手册
2-40 HP Portable Chillers
Chapter 7: Appendix
57 of 70
Remote Condenser Assembly Models
To convert inches to cm, multiply dimension by 2.54.
Fan(s)
d e f Remote
Condenser
Refrigeration
g
Each
Totals
e f Overall
Dimensions Connections
Charge
HP Dia.
Motor
Amps
Air
flow
Net
wt.
Length Width Height
Mtg. Discharge Liquid R-22
in. hp
c
460V
Fans
cfm
h lbs.h ‘A’(in.) ‘B’(in) ‘C’(in.) ‘D’(in) ODS(in.) ODS(in.) lbs.
g
5
26
3/4 hp 1 ø
2.4
1
6,450
260 49.8 43.0 40.5 40.0 11/8
7/8
3.6
7.5 26 1/3 hp 3 ø
3.7 2
12,400
470 69.8 43.0 40.5 60.0 11/8
7/8
3.6
10 26 1/3 hp 3 ø
3.7 2
13,700
510 89.8 43.0 40.5 80.0 13/8 11/8
4.6
15 26 1/3 hp 3 ø
5.0 3
20,500
550
129.8 43.0 40.5 120.0
15/8 11/8
6.4
20
30 1 1/2 hp 3 ø
5.9
2
23,000
840 125.0 45.5 50.0 108.0
15/8 15/8
10.0
25
30 1 1/2 hp 3 ø
5.9
2
21,900
860 125.0 45.5 50.0 108.0
15/8 15/8
16.0
30
30 1 1/2 hp 3 ø
9.4
3
34,800 1,280
180.0 45.5 50.0 i
21/8 21/8
24.0
40
30 1 1/2 hp 3 ø 12.9
4
46,400 1,690
235.0 45.5 50.0 i
21/8 21/8
29.0
c ø represents electrical phase; all motors are 1,140 rpm. Multiply hp by 0.746 to convert to kW.
d All first fan motors (Header Side) are ¾ hp (0.56 kW) single phase variable speed.
e Multiply 460V amperages by 2.0 for 208-230V amperages.
f Multiply 460 V amperages by 0.8 for 575 V amperages.
g Refrigeration charge is for remote condenser only!
h To convert cfm to cmh, multiply by 1.699. To convert lbs. to Kg, multiply by 0.454.
i See drawing above.
d All first fan motors (Header Side) are ¾ hp (0.56 kW) single phase variable speed.
e Multiply 460V amperages by 2.0 for 208-230V amperages.
f Multiply 460 V amperages by 0.8 for 575 V amperages.
g Refrigeration charge is for remote condenser only!
h To convert cfm to cmh, multiply by 1.699. To convert lbs. to Kg, multiply by 0.454.
i See drawing above.