Emerson GXT2-10000RT208 Benutzerhandbuch

Seite von 56
Configuration Program
25
8.6.3 Frequency Selection
The UPS is normally designed for 50Hz or 60Hz operation. The factory default corresponds to the 
model. All models are capable of being used as 50Hz or 60Hz systems. The UPS will Auto-sense the 
utility frequency when first plugged in and set the nominal frequency to match. Therefore, for all nor-
mal use the Auto Sense button should be selected.
Some special applications require that the UPS be used as a frequency converter. Frequency Con-
verter 50Hz mode will provide 50Hz UPS output from 60Hz commercial power. Frequency converter 
60Hz mode will provide 50Hz UPS output from 60Hz commercial power.
Note that frequency converter operation disables the Bypass. If, for any reason, the UPS inverter is 
unable to power the load, the alternate bypass to utility power will not be available and power will be 
removed from any load.
8.7
Options Tab
Computer users may choose to use versatile 
computer shutdown software that communi-
cates with the UPS via a serial communication 
cable. The Options Tab should not be used to 
modify the UPS functions for such applica-
tions.
For some industrial applications and special 
computer applications, the UPS may be moni-
tored and controlled using external voltages 
and relay contact signals. The Options tab 
expands the UPS versatility for such applica-
tions.
Refer to your UPS manual for a description of 
the nine-pin communication connector on the 
rear of the UPS. Pin 6 of the nine-pin commu-
nication connector is used for “Any Mode Shut-
down” of the UPS output. This control input 
may be used in special applications to disable 
the UPS output power—both Inverter and 
Bypass.
The Options Tab allows the behavior of the 
Any Mode Shutdown feature to be modified.
When the program opens, or the Refresh but-
ton is pressed, the UPS setting is read by the 
configuration program and displayed.
Factory Default Setting Illustrated for 
700-3000VA Models—This Options Tab illus-
tration shows the available function defini-
tions using pin 6 and the factory default settings.
!
WARNING
Auto-Enable Output
Note that when this option is selected and the UPS output is disabled using Pin 6, the UPS 
output can turn on automatically and without warning if the Pin 6 connection is changed.
!
WARNING 
Pin 6 Logic
DO NOT CHANGE THIS OPTION from the factory default setting unless you are ready to 
install a normally closed connection between Pins 5 & 6. This connection must be maintained 
to use the UPS or to use the configuration program again, including the ability to change the 
UPS setting back to the default setting using the configuration program via a serial 
communication link.