Siemens S7-400 Benutzerhandbuch

Seite von 638
Analog Modules
5-135
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
5.24.1
Commissioning the SM 431; AI 8 
  
16 Bit
You set the mode of operation of the SM 431; AI 8 
 
 16 Bit in STEP 7.
Parameter
You will find a description of the general procedure for assigning parameters to
analog modules in Section 5.7.
An overview of the parameters that you can set and their default settings are
shown in the table below.
Table 5-74 Parameters of the SM 431; AI 8 
 
 16 Bit 
Parameter
Value Range
Default
2)
Parameter
Type
Scope
Enable
Diagnostic interrupt
1)
Hardware interrupt
1)
Yes/no
Yes/no
No
No
Dynamic
Module
Destination CPU for
interrupt
1 to 4
Static
Module
Trigger for hardware
interrupt
3)
Dynamic
Channel
High limit
Low limit
32767 to – 32768
– 32768 to 32767

Dynamic
Channel
Diagnostics
Wire break
Reference channel
error
Underflow
Overflow
Yes/no
Yes/no
Yes/no
Yes/no
No
No
No
No
Static
Channel
Measurement
Measuring method
Disabled
U
Voltage
4DMU
Current 
(four-wire transmitter)
TC-L
Thermocouple (linear)
TC-L
Static
Channel
Measuring range
Refer to Section 5.24.2 for the
measuring ranges of the input
channels that you can set.
Type J
Reference
temperature
– 273.15 to 327.67 
o
C
–327.68 to 327.67 
o
F
100 
o
C
Dynamic
Module
Temperature unit
4)
Degrees Celsius; degrees Fahrenheit
Degrees
Celsius
Interference
suppression
400 Hz; 60 Hz; 50 Hz; 10 Hz
60 Hz
Static
Module