Siemens S7-400 Benutzerhandbuch

Seite von 638
Analog Modules
5-136
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Table 5-74 Parameters of the SM 431; AI 8 
 
 16 Bit, continued
Parameter
Scope
Parameter
Type
Default
2)
Value Range
Smoothing
None
Low
Average
High
None
Reference junction 
(reference to the cold
junction)
None
Internal
Reference temperature value dynamic
Internal
Static
Module
1)
If you use the module in ER-1/ER-2, you must set this parameter to “No” because the interrupt lines are
not available in ER-1/ER-2.
2)
Only in the CC (central controller) is it possible to start up the analog modules with the default settings.
3)
The limit values must be within the temperature range of the connected sensor.
4)
Valid for the format of the output temperature and the dynamic reference temperature
Smoothing of the Measured Values
You fill find information that is generally applicable to the smoothing of analog
values in Section 5.6.
The cycle time of the module is a constant in the  SM 431; AI 8 
 
 16 Bit that is not
dependent on the number of channels that are enabled. It therefore has no effect
on the step response, which is defined by the parameter assignment of
interference frequency suppression and smoothing.
Step Response
Table 5-75 How Response Times Depend on the Parameterized Interference Frequency Suppression
and Smoothing of the SM 431; AI 8 
 
 16 Bit 
Interference Frequency
S pp essio  i  H
Response Time in ms with Parameterized Smoothing:
Suppression in Hz
None
Low
Average
High
10
100
200
1600
3200
50
20
40
320
640
60
16.7
33.3
267
533
400
10
20
160
320
The following figures illustrate the contents of Table 5-75. They show the response
time required for a step response before the smoothed analog value is almost
applied to 100%. The figures apply to every change of signal at an analog input.