Delta Electronics DOP-A/AE/AS Verbindungsanleitung

Seite von 137
Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series 
Revision January, 2008, Doc. Name: 2007PDD23000007 
 
 
1-71 
Mirle FAMA SC 
A. HMI factory settings 
Baud rate: 9600, 7, EVEN, 1. 
Controller station number: 0. 
Control area/status area: 40100 / 40200. 
B. Definition of controller Read/Write address 
Registers 
Read/Write Range 
Register Type 
Format 
Word No. 
Bit No. 
Data Length 
Output Registers 
Wn 
n: 40001 ~ 50000 
N/A 
Word 
Input Registers 
Wn 
n: 30001 ~ 40000 
N/A 
Word 
¾
  Input Registers is “read only”. 
Contacts 
Read/Write Range 
Contact type 
Format 
Word No. 
Bit No. 
Discrete Outputs 
Bn 
N/A 
n: 1 ~ 10000 
Discrete Inputs 
Bn 
N/A 
n: 10001 ~ 20000 
¾
  Discrete Inputs is “read only”. 
C. Connections (Connector Pinouts) 
RS-232 
DOP Series 
9 pin D-SUB male 
(RS-232) 
Controller 
9 pin D-SUB male 
(RS-232) 
Controller 
9 pin D-SUB male 
(RS-232) 
RXD (2)
(3) TXD
TXD (3)
GND (5)
(2) RXD
(5) SG
 
 
 
 
 
 
 
 
Top View 
 
Pin1