Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
 
1-72  
Revision January, 2008, Doc. Name: 2007PDD23000007 
Mitsubishi FX/FX2N PLC 
A. HMI factory settings 
Baud rate: 9600, 7, EVEN, 1. 
Controller Station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) 
communication is allowed.) 
Control area/status area: D0 / D10. 
NOTE
 
1)  If connecting to Mitsubishi FXxN series PLC, the user can use both FX2N and FX series communication 
protocol. 
2)  If connecting to Mitsubishi FX series PLC, the user can only use FX series communication protocol. 
3)  Some registers of Mitsubishi PLCs are “read only”, however, when you write these “read only” registers, 
PLCs will not report any communication error to HMI and this will cause HMI errors. Please be aware of 
this when editing PLC program (this normally occurs when using FX series protocol when connecting to 
a FXxN series PLC). 
4)  If connecting to Mitsubishi FXxN series PLC, it is recommended for the user to use FX2N protocol. 
B. Definition of controller Read/Write address 
Registers 
Read/Write Range 
Register Type 
Format 
Word No. 
Bit No. 
Data length 
Auxiliary Relay 
Mn 
n: 0 ~ 3064 
N/A 
Byte 
Special Auxiliary Relay 
Mn 
n: 8000 ~ 8248 
N/A 
Byte 
Status Relay 
Sn 
n: 0 ~ 992 
N/A 
Byte 
Input Relay 
Xn 
n: 0 ~ 360(octal) N/A 
Byte 
Output Relay 
Yn 
n: 0 ~ 360(octal) 
N/A 
Byte 
Timer PV 
Tn 
n: 0 ~ 255 
N/A 
Word 
16-bit Counter PV 
Cn 
n: 0 ~ 199 
N/A 
Word 
32-bit Counter PV 
Cn 
n: 200 ~ 255 
N/A 
Double Word 
Data Register 
Dn 
n: 0 ~ 7999 
N/A 
Word 
Special Data Register 
Dn 
n: 8000 ~ 8255 
N/A 
Word 
¾
  Auxiliary Relay/ Special Auxiliary Relay/ Status Relay/ Input Relay /Output Relay: Address must be the 
multiple of 8.