Toshiba LF410/LF602 User Manual

Page of 16
  
No. 
EJL-114B 
 
Introduction 
The electromagnetic flowmeter uses Faraday’s Law of 
electromagnetic induction to measure the process flow. 
The device consists of two units: a detector, through 
which the fluid to be measured flows and in which 
low-level signals proportional to flow rates are 
obtained; and a converter, which supplies excitation 
current to the detector, and amplifies the signals from 
the detector and then processes and converts the 
signals into the 4–20mAdc current signal  or 
communication signal. Thanks to the unique patented 
magnetic field distribution technology, the meter is 
highly immune for upstream flow disturbances. 
Combined with multi-functional converter LF600 
(combined type) or LF602 (separate type) equipped 
with its original noise-suppression circuit and 
arithmetic operation capability, LF410 has high 
tolerance to noise, giving stable output even for slurry 
fluid measurement. IR (Infrared) switches enable 
parameter setting of the converter without removing 
the cover. Flow direction can be set in either way, and 
its 128 x 128 dot matrix LCD display allows the LCD 
rotated to 90, 180 and 270 degrees with a software. 
The AF900 hand-held terminal (HART*
communicator) can be used to communicate with the 
flowmeter from a remote place. PROFIBUS-PA*
 
interface is available as option. 
*1: HART protocol (Highway Addressable Remote 
Transducer) is a communication protocol for industrial 
sensors recommended by the HCF
 
(HART
 
Communication
 
Foundation). 
*2: PROFIBUS is the communication protocol for the 
factory automation and process automation that 
PROFIBUS Organization recommends. Instead of 
analog control with a conventional analog signal 
(4-20mA), it is one kind of the fieldbus which digitized 
all signals. Flowmeters support PROFIBUS-PA. 
 
Power  
supply 
Converter 
I/O 
Detector 
Combined type 
LF410/LF600 
LF414/LF600 
Converter 
Power 
supply
Signal cable 
Detector 
Separate type
LF410/LF602 
LF414/LF602 
Terminal box 
I/O 
 
Figure1.  Configuration 
  
 
 
LF410/LF600   
LF410   
LF602 
LF414/LF600 LF414 
Figure2.  LF410 series Flowmeters 
            
         
 
 
Specifications 
 Overall Specifications 
Measurement range in terms of flow velocity: 
0
 
 
0.3
 
m/s to 0
 
–10
 
m/s (0
 
–1.0
 
ft/s to 0
 
 
32.8
 
ft/s). 
0
 
 
0.1
 
m/s to 0
 
 
0.3
 
m/s (0
 
 
0.3
 
ft/s to 0
 
 
1.0
 
ft/s) 
range is available optionally. 
Accuracy: See the following graph. 
Pulse output: 
Vs > 0.5 m/s (1.64 ft/s): +/-0.5 % of rate. 
Vs < 0.5 m/s (1.64 ft/s): +/-0.3% of rate  
+/- 1 mm/s (0.039 inch/s). 
Current output: plus +/-8 uA (0.05 % of 
span)
 
Note: Span = Range in the magmeters. 
 
0.0
1.0
2.0
3.0
4.0
5.0
0
1
2
3
Flow Velosity (m/s)
Error
(% of rate)
Absolute figure
 
 Accuracy
 
Note: The accuracy above is measured under standard 
operating conditions using the weighing method 
at Toshiba's flow calibration facility. 
*3: CE mark is under application. 
Field Intelligent Device Series 
Electromagnetic Flowmeter 
 
LF410 /LF600
LF410 /LF602
15 to 200 mm (1/2" to 8")
0                                         1                                         2                                       10
*3
Certification number
Z01207