Emerson 2200S User Manual

Page of 158
106
Micro Motion
®
 Model 2200S Transmitters
Troubleshooting
10.10
I/O problems
If you are experiencing problems with the mA output, use Table 10-2 to identify an appropriate 
remedy. Simulation mode may also be helpful (see Section 10.11).
Table 10-2
I/O problems and remedies
Symptom
Possible cause
Possible remedy
No output
Loop test failed
Power supply problem
• Check power supply and power supply wiring. 
mA output < 4 mA
Process condition below LRV
• Verify process.
• Change the LRV. See Section 6.2.2.
Fault condition if fault action is set to 
internal zero or downscale
• Check the fault action settings to verify 
whether or not the transmitter is in a fault 
condition. See Section 6.2.5.
• If a fault condition is present, see Section 10.8.
Open in wiring
• Verify all connections.
Bad mA receiving device
• Check the mA receiving device or try another 
mA receiving device. See Section 10.16.
• Perform output simulation to locate the 
problem. See Section 10.11
Bad output circuit
• Measure DC voltage across output to verify 
that output is active.
• Perform output simulation to locate the 
problem. See Section 10.11
Output not powered 
• Check transmitter wiring. See the transmitter 
installation manual.
Constant mA output 
Non-zero HART address
• Set HART address to 0 or enable the Loop 
Current Mode parameter. See Section 10.19.
Output is fixed in a test mode
• Exit output from test mode. See Section 7.3.
Zero calibration failure
• Cycle power.
• Stop flow and rezero. See Section 7.2.
mA output consistently out of 
range 
Fault condition if fault indicator is set to 
upscale or downscale
• Check the fault indicator settings to verify 
whether or not the transmitter is in a fault 
condition. See Section 6.2.5.
• If a fault condition is present, see Section 10.8.
LRV and URV not set correctly
• Check the LRV and URV. See Section 10.20.
Consistently incorrect mA 
measurement
Scaling mismatch between transmitter 
and host.
• Ensure that the host is scaled for either 12–20 
mA input or 4–20 mA input, as appropriate to 
your installation. See Section 8.3.
Output not trimmed correctly
• Trim the output. See Section 7.4.
Incorrect flow measurement unit 
configured
• Verify flow measurement unit configuration. 
Incorrect process variable configured
• Verify process variable assigned to mA output. 
LRV and URV not set correctly
• Check the LRV and URV. See Section 10.18.
mA reading correct at low 
currents but wrong at higher 
currents 
mA loop resistance may be too high
• Verify mA output load resistance is below 
maximum supported load (see installation 
transmitter manual).