To configure Added Damping:
Using the Communicator, select 
Detailed Setup > Config Outputs > Channel Setup > 
AO Setup
.
Using ProLink II, click 
ProLink > Configuration > Analog Output
.
Note: You cannot configure Added Damping with the display.
6.2.5
mA output fault action and fault value
The Fault Action parameter specifies the state to which the mA output will be forced if the transmitter 
encounters an internal fault condition. Options are shown in Table 6-4.
 
Example
Configuration:
Flow Damping: 1
mA output process variable: Mass flow
Added Damping: 2
As a result, a change in mass flow will be reflected in the mA output 
over a time period that is greater than 3 seconds. The exact time 
period is calculated by the transmitter according to internal algorithms 
which are not configurable. 
Table 6-4
mA output fault actions and values
Fault action
Output scale
Fault output value
Upscale
N/A
21–24 mA (user-configurable; default: 22 mA)
Downscale
12–20 mA
10.5–11.8 mA (user-configurable; default: 11.0 mA)
4–20 mA
1.0–3.6 mA (user-configurable; default: 2.0 mA)
Internal zero
N/A
Goes to the mA output level associated with a process variable value of 0 
(zero), as determined by URV and LRV values.
None
N/A
Tracks data for the assigned process variable; no fault action
When configuring fault behavior, ensure that the configured fault action does not cause measurement 
error or process upset, and that your control system can recognize fault conditions. For fault indication, 
use the appropriate combination of mA output fault action, digital communications fault action, and 
checking status via digital communications (e.g., HART command 48).
If you set the mA Output Fault Action to None, be sure to set the Digital Communications Fault Action to 
None (see Section 6.3.1). If you do not, the mA output will not report actual process data, and this may 
result in measurement error or unintended consequences for your process.