Emerson 2200S User Manual

Page of 158
Configuration and Use Manual
67
Integrating the Meter with the Control System
Op
eratio
n
App
e
ndi
ces
Mai
n
tenan
c
e and
 T
roub
le
sh
oo
tin
g
Com
m
is
si
on
in
g
6.3.1
Digital communications fault action
The Digital Communications Fault Action parameter specifies the values that will be reported via 
digital communications if the transmitter encounters an internal fault condition. Table 6-5 lists the 
options for Digital Communications Fault Action.
Configuration
To configure the digital communications fault action:
Using the Communicator, select 
Detailed Setup > Config Outputs > Comm Fault Ind
.
Using ProLink II, click 
ProLink > Configuration > Device
.
Note: You cannot configure Digital Communications Fault Action with the display.
6.3.2
Loop current mode 
The Loop Current Mode parameter is used to fix or unfix the mA output:
If the Loop Current Mode parameter is disabled, the mA output from the transmitter is fixed at 
12 mA and therefore cannot be used to report process data. If the Micro Motion 
adapter-barrier is installed, the mA output will appear to be fixed at 4 mA.
If the Loop Current Mode parameter is enabled, the mA output will report process data as 
configured.
Table 6-5
Digital communications fault actions and values
Fault Action code
Fault output value
Communicator
ProLink II
Upscale
Upscale
• Process variables indicate the value is greater 
than the upper sensor limit. 
• Totalizers stop incrementing.
Downscale
Downscale
• Process variables indicate the value is less than 
the lower sensor limit. 
• Totalizers stop incrementing.
IntZero-All 0
Zero
• Flow rates go to the value that represents a flow 
rate of 0 (zero). 
• Density and temperature reported as 0.
• Drive gain reported as measured. 
• Totalizers stop incrementing.
Not-a-Number
Not-A-Number (NAN)
• Process variables report IEEE NAN. 
• Drive gain reported as measured.
• Modbus scaled integers report 
Max Int
• Totalizers stop incrementing.
IntZero-Flow 0
Flow to Zero
• Flow rates reported as 0. 
• Other process variables reported as measured.
• Totalizers stop incrementing.
None
None (default)
• All process variables reported as measured.
• Totalizers increment if started.
If you set the mA Output Fault Action to None (see Section 6.2.5), be sure to set the Digital 
Communications Fault Action to None. If you do not, the mA output will not report actual process data, 
and this may result in measurement error or unintended consequences for your process.