Security seal installation
Section 3: Electrical installation
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual
May 2015
3-9000-765 Rev H
3.7
Security seal installation
Security seals protect the integrity of the meter metrology and prevent tampering with 
transducer assemblies. The following sections detail how to properly seal the Daniel 3812 Liquid 
Ultrasonic Flow Meter after commissioning. The security seal wires are commercially available. 
Be sure to set the WRITE PROT. switch on the CPU Module to the ON position prior to sealing the 
enclosure.
3.7.1
Direct or remote mount transmitter electronics enclosure 
seal
Use the following instructions to install the security seal wires on the Transmitter Electronics 
Enclosure.  
Figure 3-8  Transmitter electronics enclosure security latch 
CUTTING HAZARD
Sharp edges may be present on the band shrouds.
Wear  appropriate  personal  protective  equipment  when  working  on  the  meter.  Failure  to  do  so  may 
cause serious injury. 
A.
A.  Transmitter Electronics Enclosure end cap
B.  Security latch 
B.