Weber SILVER D User Manual

Page of 6
4
GAS LINE PIPING
•  Refer to the piping chart at the bottom of previous page.
•  The corrugated gas line from the manifold is 58 inches 
long. Do not extend the gas line. 
•  We have provided the means to make an SAE 45° flare 
connection. Do not use pipe sealant on this connection.
•  If the length of line required does not exceed 50 feet, 
use a 5/8” O.D. tube. One size larger should be used for 
lengths greater than 50 feet. Refer to piping chart.
•  Gas piping may be copper tubing, type K or L; polyethyl-
ene plastic tube, with a minimum wall thickness of .062 
inch; or standard weight (schedule 40) steel or wrought 
iron pipe.
•  Copper tubing must be tin-lined if the gas contains more 
than 0.3 grams of hydrogen sulfide per 100 cubic feet of 
gas. 
•  Plastic tubing is suitable only for outdoor, underground 
use.
•  Gas piping in contact with earth, or any other material 
which may corrode the piping, must be protected against 
corrosion in an approved manner.
•  Underground piping must have a minimum of 18” cover.
TEST CONNECTIONS 
All connections and joints must be thoroughly tested for leaks 
in accordance with local codes and all listed procedures 
in the latest edition of the National Fuel Gas Code ANSI 
Z223.1/NFPA 54.
DANGER 
Do not use an open flame to check for gas leaks. 
Be sure there are no sparks or open flames in the 
area while you check for gas leaks. This will result 
in a fire or explosion which can cause serious 
bodily injury or death, and damage to property.
Typical 20 LP propane gas supply Instal-
lation
We strongly recommend that you use the Summit
®
 Built-In 
Tank Cabinet (#21280) for installations using a 20 lb LP cylin-
der, mounted remotely in an “island” structure.
The Summit
®
 Built-In Tank Cabinet is a CSA listed acces-
sory for installing a remote mounted 20 lb LP cylinder, in an 
“island” structure. Summit
®
 Built-In Tank Cabinet has a hose 
and regulator assembly and gas connections, for connecting 
a remote mounted LP cylinder to the Summit
®
 Built-In gas 
grill. The hose and regulator is listed as a required part of the 
CSA listed Summit
®
 Built-In gas grill.
The Summit
®
 Built-In Tank Cabinet also meets the require-
ments for venting, tank retention and separation of the LP 
cylinder from a heat source as outlined in the ANSI Standard 
for Outdoor Cooking Gas Appliances, Z21.58/CSA 1.6 for LP 
enclosures.
GAS SUPPLY
The Summit
®
 Built-In Tank Cabinet has its own installation 
guide.
If you do not use the Summit
®
 Built-In Tank Cabinet, you 
need to hire a licensed contractor or licensed plumber and 
they need to follow the requirements described in the ANSI 
Standard for Outdoor Cooking Gas Appliances, Z21.58/CSA 
1.6 for LP enclosures.
The requirements described in the Standard for Outdoor 
Cooking Gas Appliances, Z21.58/CSA 1.6. are as follows;
A remote enclosure for an LP gas cylinder shall be ventilated 
by openings at both the upper and lower levels of the cylinder. 
This shall be accomplished by one of the following:
a).  One side of the remote LP cylinder enclosure shall be 
completely open; or 
b).  If the remote LP cylinder enclosure is designed to have 
four sides, a top and a bottom, ventilation is required for 
the remote LP cylinder enclosure;
1).  There should be at least two ventilation openings, 
(a hole or group of holes, for the purpose of ventila-
tion) in the sidewalls of the enclosure. The openings 
should be located within 5 inches (127mm) of the 
top of the enclosure. The ventilation openings should 
be equally sized and spaced at a minimum of 90 
degrees, and be unobstructed. The openings shall 
have a total free open area of not less than 20 square 
inches. (This relates to1 square inch of ventilation 
area, per pound of stored fuel capacity).
2).  Ventilation openings (a hole or group of holes, for the 
purpose of ventilation) should be provided at floor 
level. The ventilation openings should have a total 
free area of not less than 10 square inches. (This 
relates to  square of ventilation area, per pound of 
stored fuel capacity). There should be at least two 
ventilation openings if the ventilation openings at floor 
level are in the sidewall. The ventilation openings 
should be within 5 inches (127mm) of the floor. The 
ventilation openings should be of equal size and be 
spaced at a minimum of 90 degrees, and should be 
unobstructed. 
3).  The minimum size of the ventilation hole (s) should 
not be less than  inch. 
4).  The ventilation openings in the sidewalls should not 
allow venting into the empty or “hollow” area of the 
“island”. If a gas leak should occur or the LP cylinder 
should vent in the LP cylinder enclosure, the gas 
should not be allowed to vent or migrate into the 
empty or “hollow” area of the “island”.  Ventilation 
openings in the sidewalls of the enclosure should 
only communicate with the outside of the “island” 
structure, so that the gas can dissipate outside of the 
“island” structure. 
c).  If the remote LP cylinder enclosure has four sides, a top 
and a bottom, and is intended for installation in a built-in 
“island” enclosure;