Note:
Grounding the SITRANS LC 500 as illustrated above provides only system
grounding for referencing purposes: it does not provide safety grounding.
Cathodically
Protected Metal
Tanks
Cathodically protected metal tanks
are never directly grounded.
However, the impedance of the
supply source is so low that it will
not cause any problems. The
shielding of the loop cable should
be grounded at one end only (the
tank end) to avoid short-circuiting
the cathode protection voltage.
The ground lug on the
SITRANS LC 500 can be connected
to the tank as shown.
(See page 27 for further grounding
details.)
metal
ground lug
optional stilling
well
V
KP
Non-Conductive Tanks
Non-metallic tanks always require a
stilling well or proper grounded
conductive medium.
Connect the ground lug on the
SITRANS LC 500 to earth ground. If
the stilling well is integral to the
SITRANS LC 500, it is now grounded.
If the vessel has a stilling well
provided, make sure that the metal
parts of the stilling well are properly
grounded.
ground lug
stilling well
non-
metallic