Entering Operating Parameters to Select Modes
To enter the display:
1.
Press the
Mode Display key to view the Run/Stop & Alarm 1 Modes.
2.
Press
and
to set the higher or lower the values of the parameter or turn that
function On or Off.
The
SV readout
displays the different values for the parameter within a mode.
3.
To switch modes within a level, press and hold the
Level Display key for one (1)
second.
The
PV
readout will display the different parameters within each mode.
4.
Use short presses on the
Mode Display key to display each parameter within a mode.
The
SV
readout displays the different values for the parameter within a mode.
5.
Press
and
to set the higher or lower the values of a parameter or turn that
function On or Off.
6.
Press
Level Key once to return to the Process Temperature Setting.
Figure 6: Settings for Process Temperature Controller (E5CN), Part No. A0567917
Mode
Parameter
Setting range
Default
Manuf. setting
Run/Stop Run/Stop Run
-
Operation
Alarm value 1
-1999 to 9999
0
35
Mode
Parameter
Setting range
Default
Manuf. setting
AT execute/cancel
ON, OFF
OFF
?
Temperature input shift
-199.9 to 999.9
0.0
-
Proportional Band
0.1 to 999.9
8.0
?
Integral Time
0 to 3999
233
?
Adjustment
Derivative Time
0 to 3999
40
?
Dehumidifying Dryers
Chapter 4: Operation
24 of 53