Sterling 882.00290.00 User Manual

Page of 53
Redundant Safety Controller Display 
Optional 
The Redundant Safety Controller limits the process air temperature from exceeding the upper 
temperature range set by the E5CN Temperature Controller. Standard dryers use a 
microprocessor-based controller for limiting the process air temperature. The controller is a 
modular, self-contained unit removable from the mounting housing. All parameters are 
factory set and adjusted; normally, no field adjustment to the internal controls are necessary. 
Figure 8:  Typical Redundant Safety Controller Display; Part No. A0568961 
 
 
Setting the Redundant Safety Controller 
The Redundant Safety Controller alarm setting is changed by pressing the up and down keys 
to input the alarm value. The upper display reading indicates the Process Value, while the 
lower display indicates the High Point Setting alarm value.  The factory setting for the High 
Point Alarm Value 
(L1-hi )
 is 150
°F (-23°C). 
Restoring the WATLOW Redundant Safety Controller to Factory Setup 
If the preset parameters on the controller have been tampered with and it no longer functions 
properly, see page 28 for Factory Default.  This controller is not meant to be modified. 
WATLOW Operating Parameters 
The WATLOW controller has only one mode selection; ALARM
The factory sets the security level to protect the critical parameters from being accidentally 
changed. Below is an explanation of the modes you will have access to and the manufacturer 
default settings. 
 
 
 
 
 
 
 
 
 
 
Dehumidifying Dryers 
Chapter 4: Operation 