Sterling 882.00290.00 User Manual

Page of 53
Entering Operating Parameters to Select Modes 
To enter the display: 
1. 
Press both the Up 
 and Down 
 keys for three seconds from the home page.  The word 
SEE will appear in the upper display and PAGE will appear in the lower display. 
2. 
Press the Advance Key  
 to move through the parameter prompts. 
3. 
Press the Up 
 or Down 
 keys to change the parameter value. 
4. 
Press  the RESET Key at any time to return to the Home Page display. 
Figure 9:  Setting List for Redundant Safety Controller (WATLOW), Part No. A0568961 
 
Mode 
Parameter 
Setting range 
Default 
Manf. setting 
SEn Sensor 
Type 
0-3 
Lin 
Thermocouple Linearization  0-10 
H (1) 
C-F 
Temperature Units 
Fahrenheit / Celsius 
S.dEC 
Temp. Decimal Places 
0 – 0.0 
IS.En 
INFOSENSE™ 
Yes / No 
No 
Sc.Lo 
Process Scale Low 
4.00 to 20.00 mA   
1.00 to 10.00V  
4.00 mA 
1.00V 
Sc.hi 
Process Scale High 
4.00 to 20.00 mA 
1.00 to 10.00V 
20.00 mA 
5.00 V 
400 
CAL Calibration 
Offset 
-999 to 999 
Ftr.E Input 
Filter 
Off, 
DiSP, Cont, both 
OFF 
Ot 1 
Output 1 Function 
Limit (2) 
(2) 
LSd1 
Output 1 Limit Sides 
Both, High, Low 
Both 
High 
hyS1 
Limit 1 Hysteresis 
0.0 to 999.0 
1.0 
Ot2 
Output 2 Function 
Off / Process Alarm / Limit (2)  
OFF 
LSd2 
Output 2 Sides 
Both / high / low 
Both 
UdSP Upper 
Display 
Look 
None, Process Value, Limit 1 Low Set, 
Limit 1 High Set, Limit 2 Low Set, Limit 
2 High Set, Alarm 2 Low Set, Alarm 2 
High Set, Limit 3 Low Set, Limit 3 High 
Set, Alarm 3 Low Set, Alarm 3 High Set
Process - 
LdSP Lower 
Display 
Look 
None, Process Value, Limit 1 Low Set, 
Limit 1 High Set, Limit 2 Low Set, Limit 
2 High Set, Alarm 2 Low Set, Alarm 2 
High Set, Limit 3 Low Set, Limit 3 High 
Set, Alarm 3 Low Set, Alarm 3 High Set
Limit 1  
High Set 
LOC Lockout 
(0) no lockout, (1) Programming and 
Setup Page Locked, (2) Limit Set 
Points are the only Operation Page 
parameters accesible, (3) Full Lockout. 
0 2 
 
 
 
 
Dehumidifying Dryers 
Chapter 4: Operation 
27 of 53