7.5
OUTPUT ACTION
This option allows you to define the operation of the panel's four annunciator outputs.
7.5A
CUTOFF OUTPUTS
Any or all of the available outputs can be programmed here to turn off after the time specified
in OUTPUT CUTOFF TIME. See section 7.5B. To disable this option, press any SELECT key
to clear the display of output numbers and then press COMMAND.
7.5B
OUTPUT CUTOFF TIME
If a Cutoff Output is assigned in section 7.5A, you can enter a Cutoff Time of up to 15 minutes
for the output to remain on. If the output is turned off manually, the cutoff time is reset. The
Cutoff Time can be from 1 to 15 minutes. Enter zero to provide continuous output.
The Cutoff Timer is shared by all outputs. If a second output trips, the timer is not reset. Both
outputs turn off when the original time expires.
7.5C
COMMUNICATION FAILURE OUTPUT
This output is turned on when a DD or 4-2 system fails to communicate with the receiver after
three successive dial attempts. Enter zero to disable this output.
7.5D
FIRE ALARM OUTPUT
This output is turned on any time a fire type zone is placed in alarm. The output is turned off
using the Sensor Reset option while no additional fire type zones are in alarm. Enter zero to
disable this output.
7.5E
FIRE TROUBLE OUTPUT
This output is turned on any time a fire type zone is placed in trouble or when a supervisory
type zone is placed in alarm or trouble. The output is turned off when all fire and supervisory
type zones are restored to normal. Enter zero to disable this output.
7.5F
AMBUSH OUTPUT
This output is turned on any time an Ambush code is entered at a keypad. The output is
turned off using the Sensor Reset option. Enter zero to disable this output.
7.5G
ENTRY OUTPUT
This output is turned on at the start of the entry delay time. The output is turned off when the
area is disarmed or the entry delay time expires. Enter zero to disable this output.
7.5H
EXIT OUTPUT
This output is turned on any time an exit delay time starts. The output is turned off when the
system arms or when the arming has been stopped. Enter zero to disable this output.
7.5I
READY OUTPUT
This output is turned on whenever all disarmed zones are in a normal state. The output is
turned off when any disarmed zone is in a bad state. Enter zero to disable this output.
7.5J
ARMED OUTPUT
This output is turned on any time an area of the system is armed. The output is turned off
when the system is completely disarmed.
7.5K
BURGLARY OUTPUT
This output turns on any time a burglary zone is in alarm. The output is turned off when the
area in which the alarm occurred is disarmed and no other burglary zones are in alarm.
7.5L
GROUND START OUTPUT
This output turns on for 750ms any time the panel seizes the telephone line. Enter zero to
disable this output.
 7 - OUTPUT OPTIONS
OUTPUT ACTION . . .
CO OUTS:  -  -  -  -
READY  OUT:
0
EXIT OUT:
0
BURGLARY OUT:
0
FIRE ALR  OUT:
0
GROUND START:
0
ARMED OUT:
0
AMBUSH OUT:
0
ENTRY  OUT:          0
COM  FAIL OUT:
0
FIRE  TRB  OUT:
0
CUTOFF  TIME:
0