DMP Electronics Command Processor Panel User Manual

Page of 26
1
2841 E. Industrial Drive  Springfield, MO  65802-6310  800-641-4282
XR10 Programming Guide
   1-INTRODUCTION
Introduction
1.1
Before You Begin
About this Guide
This guide provides programming information for the DMP XR10 Command Processor Panel. After this Introduction,
the remaining sections describe the functions of each programming menu item along with their available options.
Before starting to program, we recommend you read through the contents of this guide. The information contained
here allows you to quickly learn the programming options and operational capabilities of the XR10 panel.
In addition to this guide, you should also read and be familiar with the following XR10 documents:
XR10
 
User's Guide (LT-0226)
XR10 Installation Guide (LT-0229)
XR10 Product Specification (LT-0228)
Internal Programmer
The XR10 panel contains all of its programming information in an on-board processor and does not require an
external programmer. You can perform all programming tasks through a keypad connected to the system.
Programming Information Sheets
Included with each XR10 panel is a Programming Information Sheet. This lists the various keypad prompts and
available options for programming the panel. Before starting to program, we recommend you completely fill out the
sheet with the programming options you intend to enter into the panel.
Having a completed programming sheet available while entering data helps prevent errors and can shorten the time
you spend programming. A completed programming sheet also provides you with an accurate record of the panel's
program you can keep on file for future system service or expansion. The remainder of this Introduction tells you how
to start and end an XR10 programming session.
1.2
Getting Started
Before you begin programming, make sure the XR10 panel is properly grounded and AC and battery power is applied
to the appropriate panel terminals. All wiring connections and grounding instructions are detailed in the XR10
Installation Guide (LT-0229).
Initializing the Panel
When programming an XR10 panel for the first time, or rewriting the entire program of an existing XR10, use the
Initialization function described in section 2. Initializing clears the panel's memory of any old or incorrect data.
Accessing the Programmer
To access the programmer function of the XR10:
1. Place a slotted screwdriver across the two J16 reset jumpers for two seconds.
2. Remove the screwdriver.
3. Enter the code 6653 (PROG) into the keypad.
4. Enter your Access Code.
5. The keypad displays: PROGRAMMER.
You are now ready to start programming the XR10 panel. Pressing the COMMAND key scrolls you through the
programming menu items listed in section 1.3.
1.3
Programming Menu
There are 9 programming menu items to choose from:
Menu Item
Section
Menu Item
Section
Initialization
2
Output Options
7
Communication
3
Zone Information
8
Remote Options
4
Stop
9
System Reports
5
Set Lockout Code
10
System Options
6
To select a section for programming, press any top row SELECT key when the name of that section is displayed on
the keypad. The detailed instructions for each programming step are found in the following sections.