Object 0x6067: Position window  
This object defines a symmetrical range of accepted positions relative to the target 
position
. If the actual value of the position encoder is within the position window, this target 
position
 is regarded as reached. Because the position window is usually specified in user-
defined units, the position factor must be used to transform this value into increments. 
Before it can be used with this function, the target position must be handled in the same 
manner as in the trajectory generator for limiting functions and transformation into 
internal machine units. 
  The Elmo drive always checks the target position window in its own setup 
parameters TR[1] and TR[2] at the real-time level. Therefore, the following points 
must be taken into account: 
 
The position error mechanism cannot be switched off. 
 
The limits of the position window and the position window time (in internal units) 
are 32,000 increments and 100 milliseconds, respectively. 
 
Object description: 
Index 6067h 
Name Position 
window 
Object code 
VAR 
Data type 
UNSIGNED32 
Category Optional 
 
Entry description: 
Access Read/write 
PDO mapping 
No 
Value range 
UNSIGNED32 
Default value 
No 
 
Object 0x6068: Position window time 
When the actual position is within the position window during the defined position window 
time
 — given in multiples of milliseconds — the corresponding bit 10 target reached in the 
statusword is set to 1. Refer to the description in the position window object. 
 
Object description: 
Index 6068h 
Name 
Position window time 
Object code 
VAR 
Data type 
UNSIGNED16 
Category Optional 
CANopen DSP 402 Implementation Guide 
 
MAN-CAN402IG (Ver. 1.2) 
 
 