Installation
XR6A/XR10A/XR20A Installation Guide
2841 E. Industrial Drive  Springfield, MO  USA  65802-6310  800-641-4282
Digital Monitoring Products
Reset Jumpers J16
14.1 Description
There are two reset jumpers located at the top right of the panel's circuit board labeled RESET. Momentarily
shorting these jumpers allows you to reset the microprocessor of the XR6A/XR10A/XR20A. Resetting the panel
allows you to enter the panel's internal programmer.
To reset the panel when first installing the system, place the blade of a slotted screwdriver across the two reset
jumpers after applying power to the panel.
To reset the panel while the system is operational (for example, prior to reprogramming), you can short the
jumpers without powering down the system.
After resetting the panel for programming, you must begin within 30 minutes. If you wait longer than 30 minutes,
you'll have to reset the panel again.
Troubleshooting Section
15.1 Description
This section of the XR6A/XR10A/XR20A Installation Guide provides troubleshooting information for use when
installing or servicing an XR6A/XR10A/XR20A system.
Problem
Possible Cause
Solution
Security Command keypads
display " SERVICE REQUIRED"
J16 reset jumper is installed.
Open or short on the green data
wire to the keypad.
Bad keypad or zone expander.
Remove the J16 reset jumper.
Check for broken or shorted wires
between the keypad and panel.
Replace with a new or repaired
keypad or zone expander.
Open or short condition on the
yellow data wire.
Bad keypad or zone expander.
Check for broken or shorted
wires.
Replace with a new or repaired
keypad or zone expander.
Keypad beeps when keys are
pressed but won't allow the user
to arm or enter the User Menu.
Keypad display is not functional.
When a key is pressed, only a
short beep is emitted.
Set each keypad to a different
address to match the Device
Setup programming.
Two or more keypads are assigned
to the same address.
Page 13