DMP Electronics XR10A User Manual

Page of 18
Introduction
XR6A/XR10A/XR20A Installation Guide
2841 E. Industrial Drive  Springfield, MO  USA  65802-6310  800-641-4282
Digital Monitoring Products
Panel Specifications
1.1
Power supply
Transformer Input: 16.5 VAC  40VA or 16.5 VAC  20VA
Standby Battery: 12 VDC 7.0Ah (40VA transformer charges up to 2 batteries)
Auxiliary Output: 12 VDC at 500mA
Bell Output: 12 VDC at 1.5 Amps with 40VA transformer, 600mA with 20VA transformer
Smoke Detector Output: 12 VDC at 100mA
All circuits inherent power limited
1.2
Communication
Built-in SDLC Digital Dialer communication to DMP Model SCS-1 Receivers
Built-in 4-2 communication to non-DMP receivers
Built-in M2E (Radionics Modem IIe) communication to non-DMP receivers (XR20A only)
Built-in CID (Contact ID) communication to non-DMP receivers
All panels can operate as a local system.
1.3
Panel zones
Nine 1k 
W
 EOL burglary zones (zones 1 to 9), (zones 1 to 5 on XR6A)
One 3.3k 
W
 EOL Class B powered fire zone with reset capability (zone 10 on XR10A and XR20A), (zone 6 on
XR6A)
1.4
Keypads
You can connect up to four of the following supervised keypads to the XR6A/XR10A/XR20A panels.
• 16 or 32 character alphanumeric keypads
• 10-zone LED keypads
In addition, four and single point zone expanders can be added to the XR20A panel.
When using the FA426 Wireless Receiver, the XR20A allows unsupervised devices to be added to address five.
1.5
Outputs
The XR6A/XR10A/XR20A panels provide four open collector outputs rated for 50mA each. See section 12.1. A
Model 300 Wire Harness is required. The open collector outputs provide the ground connection for a positive
voltage source.
1.6
Enclosure specifications
The XR6A/XR10A/XR20A panel ships in an enclosure with EOL resistors, battery leads, user's guide, and
programming sheet.
Size:
12.5" W x 9.5" H x 2.75" D
Weight:
4 lbs
Color:
Gray or Black
Construction:
20 gauge cold rolled steel
Page 1