Omron FQM1-MMA21 User Manual

Page of 414
118
Operation Settings at Startup and Maintenance Functions
Section 5-7
5-7
Operation Settings at Startup and Maintenance Functions
This section describes the following operation settings at startup and mainte-
nance functions.
• Operating mode at startup
• Program protection
• Remote programming and monitoring
• Flash  memory
5-7-1
Specifying the Startup Mode
The operating mode when the power is turned ON can be specified in the
System Setup.
System Setup
Note
The operating mode at startup for Motion Control Modules will be the same as
that for the Coordinator Module when in Sync Mode, but will be RUN mode
when in ASync Mode.
5-7-2
Program Protection
The FQM1 provides the following kinds of protection for user programs.
Read Protection 
Using Passwords
Read and display access to the user program area can be blocked from the
CX-Programmer. Protecting the program will prevent unauthorized copying of
the program and loss of intellectual property.
A password is set for program protection from the CX-Programmer and read
access is prevented to the whole program.
Note
(1) If you forget the password, the program in the FQM1 cannot be trans-
ferred to the computer.
(2) If you forget the password, programs can be transferred from the comput-
er to the FQM1. Programs can be transferred from the computer to the
FQM1 even if the password protection has not been released.
Power ON
Tab page
Name
Details
Settings
Default
Startup Startup 
Mode
Specifies the 
initial operating 
mode when the 
power is turned 
ON.
System Setup disabled
• RUN mode
System Setup enabled
• PROGRAM mode
• MONITOR mode
• RUN mode
System Setup 