ENFORCER Delayed Egress Timer 
 
8
 
                                                        SECO-LARM U.S.A., Inc.
 
 
 
 
 
 
 
 
 
 
 
Remote Alarm Relay Output: 
 
The SA-025EQ is equipped with a 10A@24VDC Form C dry relay output for a  
remote alarm. 
 
The remote alarm relay is normally energized. The onboard screen print refers to the 
energized state as normal. 
 
A remote alarm connected to this output will begin signaling at the start of the  
pre-delay timer. 
 
The remote alarm will continue signaling until the door is relocked. 
 
In the event of power loss, the remote alarm relay will de-energize to trigger the  
remote alarm. 
 
The remote alarm will signal when the pre-delay bypass is activated. 
 
The remote alarm will also signal during free egress if the door is left open longer than  
5 seconds (door status jumper must be ON for this to occur). 
 
LED 3 (red) is on when the remote alarm relay is energized. 
Local Alarm Output: 
 
The SA-025EQ is equipped with a 500mA@12VDC transistor ground output for a  
local alarm. 
 
The local alarm output can be set for steady or pulsing by changing jumper 3 (see pg. 7) 
 
LED 4 (red) is on when the local alarm output is active. 
Lock Relay Output: 
 
The SA-025EQ is equipped with a 10A@24VDC Form C dry relay output that can be used 
with a fail-safe or fail-secure lock. 
 
The lock relay is normally energized. The onboard screen print refers to the energized state 
as normal. 
 
In standard mode, the lock relay will de-energize after the pre-delay time expires. The lock 
relay will re-energize when the reset input is activated. 
 
In BOCA mode, the lock relay will de-energize after the pre-delay time expires. The lock 
relay will re-energize after a door with a N.C. magnetic contact attached to the lock status 
input has been closed for 30 consecutive seconds. 
 
In timed mode, the lock relay will de-energize after the pre-delay time expires. The lock 
relay will re-energize after the post-delay time expires. 
 
LED 2 (red) is on when the lock relay is energized. 
Pre-Delay Bypass Input (N.O.+): 
 
Connect a N.O. switch between the pre-delay bypass and the positive terminal. 
 
The pre-delay bypass input bypasses the pre-delay time for immediate egress. 
 
The remote alarm and local alarm outputs are still active when the pre-delay bypass is used. 
 
The door will relock according to the relock mode.