Avaya 03-300430 User Manual
RMC-ENV (Power/Fan Sensors)
Issue 1 June 2005
1953
(e.g., fan blockage), a single event may be an anomaly that eventually clears. However, a
repeating condition causes a major alarm.
repeating condition causes a major alarm.
On-Demand Tests: Descriptions and Error Codes
Investigate tests in the order presented below. Clearing Error Codes associated with the one
test may also clear errors generated from other tests in the sequence.
test may also clear errors generated from other tests in the sequence.
Notes:
a. Refer to
on page 1944 for a description of
this test.
b. Refer to
on page 1945 for a description of this
test.
RMC Power/Fan Query Test (#77)
This test queries the Processor circuit pack for the status of the cabinet sensors in the G600
media gateway (RMC). Only one alarm lead is supported by this cabinet type to indicate a
power, temperature, or a fan problem. This means that a failure of this test can also mean a
power problem, not necessarily just a temperature/fan problem.
media gateway (RMC). Only one alarm lead is supported by this cabinet type to indicate a
power, temperature, or a fan problem. This means that a failure of this test can also mean a
power problem, not necessarily just a temperature/fan problem.
Order of Investigation
Short Test
Sequence
Long Test
Sequence
Sequence
D/ND
1
1. D = Destructive; ND = Nondestructive
RMC Power/Fan Query test (#77)
X
X
ND
Analog Ring Generator Initialization test (#117) (
)
X
X
ND
Analog Ring Generator Query test (#118) (
X
X
ND
Table 719: TEST #122 Cabinet Temperature Query Test
Error
Code
Code
Test
Result
Result
Description / Recommendation
1000
ABRT
System resources required to run this test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
2000
ABRT
Response to the test request was not received within the allowable time
period.
period.
1. Retry the command at 1-minute intervals up to 5 times.
1 of 3