Communication Manager Maintenance-Object Repair Procedures
2450 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
1950
ABRT
Another loopback/span test is already executing on the DS1 board or the 
board is in a network-requested loop-back mode (line loopback or payload 
loopback). The hardware error log will indicate whether a Customer 
Loop-Back Jack test, Far CSU Loopback test, or the One-Way Span test is 
executing or if the board is in line-loopback or payload-loop-back mode. 
Only one long-duration loopback/span test can be active at a given time. 
Thus, if a loopback/span test is already active, that test must be terminated 
using test ds1-loop location end-loopback/span-test in 
order to execute this test.
1951
ABRT
The CSU Equipment Loopback test could not be executed because the 
120A1 CSU module or the 401A T1 sync splitter was not physically 
installed. Physically connect the 120A1 CSU module or the 401A T1 sync 
splitter to the UDS1-BD board on the back of the port carrier.
2000
ABRT
Response to the test was not received within the allowable time period. 
This may be due to hyperactivity. Error Type 1538 in the error log 
indicates hyperactivity. The hyperactive circuit pack is out of service, and 
one or more of the following symptoms may be exhibited.
1. The UDS1-BD tests (such as Tests #138 and #139) are aborting with 
Error Code 2000.
2. The tests run on the ports of this circuit pack are returning a no-board 
result.
3. A busyout or a release command has no effect on the test results.
4. A list config shows that the circuit pack and the ports are 
properly installed.
When hyperactivity occurs, the circuit pack is isolated from the system, and 
all of its trunks are placed into the out-of-service state. The system will try 
to restore the circuit pack within 15 minutes. When no faults are detected 
for 15 minutes, the UDS1 interface circuit pack is restored to normal 
operation. Every UDS1 Interface trunk is then returned to the in-service 
state. Hyperactivity is often caused by the associated facility. In such a 
case, faults (such as slips, misframes, or blue alarms) would be entered in 
the error log. In addition, many hardware errors would be logged against 
the associated trunk circuits. If the facility is OK and the error occurs again 
after 15 minutes, replace the circuit pack.
2100
ABRT
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals up to 5 times.
Table 868: Test #1210 CSU Equipment Loop-Back Test  (continued)
Error
Code
Test
Result
Description / Recommendation
 2 of 3