System Event Timers 
EN | 79 
 
 
Bosch Security Systems, Inc. | 12/08 | F01U089457-02 
 
The Sensor Watch Time counter is active only when 
the control panel is disarmed. If the system is 
disarmed for 8 hours a day and the Sensor Watch 
Time is programmed for 1 day, a zone programmed 
for Sensor Watch registers a Sensor Watch Fault if it 
is not activated while disarmed within 3 days. 
This feature is useful, for example, when someone 
places objects in the view of a motion detector, which 
prevents the detector from picking up movement.  
To disable Sensor Watch Reports, program Locations 
389 and 390 as 0 (refer to Section 15.5 Zone Status – 
Sensor Watch Reports
 on page 66). 
17.8 Codepad 
Lockout 
Time 
Location 
478 
No lockout 
1 to 15 
Lockout time (increments of 10 sec) 
All codepads are locked out for the programmed 
time if an invalid code is entered more times than 
allowed by the code retry attempts programmed in 
Location 424 (refer to Section 15.26 System Status – 
Access Denied 
on page 69). If the Codepad Lockout 
Time is programmed as 0, codepad lockout does not 
occur. 
17.9  Siren Run Time 
Location 
479 
Default 
0 No 
siren 
time 
 1 to 15 
Siren time in min 
The Siren Run Time determines how long the horn 
speaker operates during an alarm. You can program 
the Siren Run Time from 0 to 15 min in 1-min 
intervals. 
17.10  Siren Sound Rate 
Location 
480 
Default 
0 Slowest 
frequency 
15 Fastest 
frequency 
The Siren Sound Rate varies the frequency of the 
siren tone slowest (0) and to fastest (15). The Siren 
Sound Rate does not change the frequency of the fire 
alarm tone. 
17.11  Auto Arming Pre-Alert Timer 
Location 
481 
Default 
No alert time 
1 to 15 
Alert time (increments of 5 min) 
This location sets the time period during which the 
control panel warns you it is automatically armed in 
AWAY Mode. The codepad beeps once every 
second until the Pre-Alert Timer expires: the system 
then automatically arms itself in AWAY Mode. If 
you want the system to automatically arm in STAY 
Mode 1, enable Option 4 in Location 496 (refer to 
Section 18.5 Consumer Options 1 on page 82). 
After the control panel is automatically armed in 
AWAY Mode or STAY Mode 1, Exit Time starts. If 
a valid User Code is entered during the Pre-Alert 
Time, the Auto Arming Time programmed in 
Locations 482 to 485 (refer to Section 17.12 Auto 
Arming Time
 on page 79) is extended by 1 hour. 
If you want a programmable output to operate 
during the Auto Arming Pre-Alert Time, use Output 
Event Type 0,5 Auto Arm Pre-Arming Alert Time 
(refer to page 71). 
17.12  Auto Arming Time 
Location
482 to 485 
 Location 
Default 
Hour of the day (tens digit) 
482 
Hour of the day (units digit) 
483 0 
Minute of the day (tens digit) 
484 
Minute of the day (units digit) 
485 0 
These locations specify the time of day the system 
automatically arms itself in AWAY Mode. Set this 
time in 24-hour format (for example, program 10:30 
PM as 2230). If you want the system to arm in STAY 
Mode 1, select Option 4 in Location 496 (refer to 
Section 18.5 Consumer Options 1on page 82).   
If forced arming is disabled for any zone, the 
automatic arming feature operates regardless of 
whether any zones are unsealed. Refer to Section 
14.3.7 Zone Options 2
 on page 63 for more 
information on programming zones for forced 
arming. 
User Code 16 is reported when this feature is used. 
For partitioned ICP-CC488 Control Panels, both 
areas are automatically armed in AWAY Mode at the 
same time each day. 
17.13 Auto Disarming Time 
Location
486 to 489
 
 
Location Default 
Hour of the day (tens digit) 
486
 
Hour of the day (units digit) 
487
 
Minute of the day (tens digit) 
488
 
Minute of the day (units digit) 
489
 
These locations specify the time of day the system 
automatically disarms itself. Set this time in 24-hour 
format (for example, program 10:30 PM as 2230).   
User Code 16 is reported when this feature is used.