Bosch ICP-CC488 User Manual

Page of 118
ICP-CC488 | Installation Guide | 18.0  
System and Consumer Options 
EN | 81 
 
 
Bosch Security Systems, Inc. | 12/08 | F01U089457-02 
 
4 – Strobe Indications for Radio Arm/Disarm 
This option allows the strobe to indicate when the 
system is armed and disarmed when remotely 
operating the system using the DSRF Series RF 
Receiver. 
 
Table 60:  Strobe Indications for Remote 
Operations 
 
Strobe Duration 
System Status 
3 sec 
System disarmed 
6 sec 
System armed in AWAY Mode 
6 sec 
System armed in STAY Mode 1 
8 – Assign Button 4 To Operate STAY Mode 4 
This option allows Button 4 on the RF3334 
4 Channel Hand Held Transmitter to arm the system 
in STAY Mode 1. 
18.2 System 
Options 
Location 
493 
Default 
Codepad Panic to be silent 
Codepad Fire to be silent 
Codepad Medical to be silent 
Access denied (code retries) to be silent 
1 – Codepad Panic To Be Silent 
If this option is selected, a Codepad Panic Alarm or 
Radio Remote Panic Alarm does not operate the 
horn speaker, the bell, or the strobe outputs. If this 
option is not selected, all three outputs operate after a 
Codepad Panic Alarm is activated when a user 
presses [1] and [3] or [STAY] and [AWAY] at the 
same time on the remote codepad. Selecting this 
option does not affect the operation of the 
communication dialer. 
If you want to disable reporting of a Codepad Panic 
Alarm, program Locations 404 and 405 as 0 (refer to 
Section 15.16 Codepad Panic Report on page 66). 
2 – Codepad Fire To Be Silent 
If this option is selected, a Codepad Fire Alarm does 
not operate the horn speaker, the bell, or the strobe 
outputs. If this option is not selected, all three outputs 
operate after a Codepad Fire Alarm is activated 
when a user presses [4] and [6] at the same time on 
the remote codepad. Selecting this option does not 
affect the operation of the communication dialer. 
If you want to disable the reporting of a Codepad 
Fire Alarm, program Locations 407 and 408 as 0 
(refer to Section 15.17 Codepad Fire Report on page 66). 
4 – Codepad Medical To Be Silent 
If this option is selected, a Codepad Medical Alarm 
does not operate the horn speaker, the bell, or the 
strobe outputs. If this option is not selected, all three 
outputs operate after a Codepad Medical Alarm is 
activated when a user presses [7] and [9] at the same 
time on the remote codepad. Selecting this option 
does not affect the operation of the communication 
dialer. 
If you want to disable the reporting of a Codepad 
Medical Alarm, program Locations 409 and 410 as 0 
(refer to Section 15.18 Codepad Medical Report on page 
68). 
8 – Access Denied (Code Retries) To Be Silent 
If this option is selected, a Codepad Tamper Alarm 
does not operate the horn speaker, bell, or the strobe 
outputs. If this option is not selected, all three outputs 
operate after a Codepad Tamper Alarm occurs. 
Refer to Section 15.26 System Status – Access Denied on 
page 69 to set the number of invalid code retries that 
causes an alarm condition. Selecting this option does 
not affect the operation of the communication dialer. 
If you want to disable the reporting of Access Denied 
reports, program Locations 424 to 426 as 0. 
18.3 System 
Options 
Location
494 
AC fail after 1 hour (disabled – after 2 min) 
2 Ignore 
AC 
fail 
Pulse count handover allowed 
Handover delay to be sequential 
1 – AC Fail after 1 Hour 
If this option is selected, the MAINS indicator flashes 
when the AC MAINS supply is disconnected. An AC 
Loss signal (Contact ID Event Code 301) is 
transmitted to the base station receiver after the AC 
MAINS supply is disconnected continuously for 
longer than 60 min. 
If this option is not selected, the MAINS indicator 
flashes and an AC Loss signal (Contact ID Event 
Code 301) is transmitted to the base station receiver 
after the AC MAINS power is disconnected 
continuously for 2 min.  
The MAINS indicator stops flashing when the AC 
MAINS supply is restored longer than 2 min.   
An AC Loss Restore Report is transmitted to the 
base station receiver after the AC MAINS supply is 
restored continuously for more than 2 min regardless 
of whether this option is selected.