Partitioning 
EN | 87 
 
 
Bosch Security Systems, Inc. | 12/08 | F01U089457-02 
 
19.6.1 
Setting Up the Master Partitioned 
Codepad as the Main Codepad 
To use the CP5 Master Partitioned (CP500P) 
codepad as the main codepad in a partitioned 
system, connect the codepad to the main codepad 
terminals (CP-, CP+, CLK, and DATA). Set all DIP 
switches on the back of the codepad to the ON 
position (refer to Figure 20 on page 87). 
19.6.2 
Setting Up an Area 1 Codepad as the 
Main Codepad 
If you are not using the CP5 Master Partitioned 
codepad as the main codepad of the partitioned 
system, connect the Area 1 codepad to the main 
codepad terminals (CP-, CP+, CLK, and DATA). Set 
DIP switch 1 on the back of the codepad into the ON 
position (refer to Figure 20 on page 87) and select 
Option 2 in Location 500 (refer to Section 19.3.1 
Partitioning Options 1 
on page 85). 
19.6.3 
Setting Up an Area 1 Codepad 
If you want a separate area codepad only for Area 1 
when using the CP5 Master Partitioned codepad as 
the main codepad, connect the Area 1 codepad to 
the main codepad terminals (CP-, CP+, and CLK) 
and connect the DATA terminal to one of the 
outputs programmed as 6,0 Area 1 Codepad Data 
(refer to page 75). Set DIP switch 1 on the back of the 
Area 1 codepad to the ON position (refer to Figure 20 
on page 87). 
19.6.4 
Setting Up an Area 2 Codepad 
If you want a separate area codepad only for Area 2, 
connect the Area 2 Codepad to the main codepad 
terminals (CP-, CP+, and CLK) and connect the 
DATA terminal to one of the outputs programmed as 
6,1 Area 2 Codepad Data (refer to page 75).  Set DIP 
switch 2 on the back of the Area 2 codepad to the 
ON position (refer to Figure 20 on page 87). 
 
 
Figure 20:  DIP Switch Location on Codepad 
 
1 – DIP Switches 
19.7 Codepad 
Connections 
For 
Partitioning - Examples 
If the CP-5 Area Addressable (CP500A) codepad is 
assigned to Area 1: 
1.  Set DIP Switch 1 on the back of the remote 
codepad to the ON position (refer to Figure 20 on 
page 87).  
2.  For Output 1, program Location 436 to 6 and 
Location 437 to 0 (refer to page 75). 
If the CP-5 Area Addressable (CP500A) codepad is 
assigned to Area 2: 
1.  Set DIP Switch 2 on the back of the remote 
codepad to the ON position. (refer to Figure 20 
on page 87).  
2.  For Output 1, program Location 436 to 6 and 
Location 437 to 1 (refer to page 75).