ICP-CC404 | Installation Guide | 15.0   System Reporting Information 
 
 
62 Bosch 
Security 
Systems, 
Inc. | 12/08 | F01U089401-02
 
A Fire Alarm Report (Contact ID Event Code 110) is 
sent to the base station receiver when a user presses 
[4] and [6] at the same time. A Fire Alarm is audible, 
but you can program the alarm as silent by selecting 
Option 2 in Location 425 (refer to Section 18.2 System 
Options 2
 on page 73). A distinct fire sound is emitted 
through the horn speaker to indicate this type of 
alarm. The fire sound is different than the burglary 
sound. 
 
 
Restore Reports are not sent for this 
event. 
If Fire Reports are not required, program 
Locations 339 and 340 as 0. 
15.11 Codepad Medical Report 
Program the Codepad Medical Report value in 
Location 341 (tens digit) and Location 342 (units 
digit). 
The default values are 
7 (tens) and 13 (units). 
A Medical Report (Contact ID Event Code 100) is 
sent to the base station receiver when a user presses 
[7] and [9] at the same time. A Medical Alarm is 
audible, but you can program the alarm as silent by 
selecting Option 4 in Location 425 (refer to Section 
18.2 System Options 2
 on page 73). 
 
 
Restore Reports are not sent for this 
event.  
If Medical Reports are not required, 
program Locations 341 and 342 as 0. 
 
15.12 Codepad Reporting Options 
Use 
Location 343 to select whether Codepad Alarm 
Reports are sent to Receiver 1 (the default), 
Receiver 2, or both, Receiver 2 only when Receiver 1 
fails, or there is no reporting at all. Table 47 lists the 
reporting options. 
 
Table 48: 
Codepad Alarm Reporting Options 
 
Option Description 
No Codepad Alarm Reports required 
1 Receiver 
Receiver 2 
Receiver 1 and Receiver 2 
Receiver 2 only when Receiver 1 fails 
15.13  System Status – AUX Power Supply 
Fail Report 
Program the AUX Power Supply Fail Report value in 
Location 344 (tens digit) and Location 345 (units 
digit). 
The default values are 
10 (tens) and 3 (units). 
A System Trouble Report (Contact ID Event Code 
300) is sent when either the codepad AUX power 
supply or the accessories AUX power supply fails. 
The system reports the event approximately 10 sec 
after the AUX power supply fails. 
15.14  System Status – AUX Power Supply 
Fail Restore Report 
Program the AUX Power Supply Fail Restore Report 
value in 
Location 346 (tens digit) and Location 347 
(units digit). 
The default values are 
10 (tens) and 8 (units). 
A System Trouble Restore Report (Contact ID Event 
Code 300) is sent when the failed codepad AUX 
power supply or the accessories AUX power supply is 
reset. The system reports the event approximately 10 
sec after the AUX power supply is reset. 
15.15  System Status – AC Fail Report 
Program the AC Fail Report value in 
Location 348 
(tens digit) and 
Location 349 (units digit). 
The default values are 
10 (tens) and 2 (units). 
An AC Fail Report (Contact ID Event Code 301) is 
sent to the base station receiver when the AC mains 
supply is disconnected for 2 min. If you do not want 
an AC Fail Report to be sent until the AC mains 
supply is disconnected for 1 hour, select Option 1 in 
Location 426 (refer to Section 18.3 System Options 3 on 
page 74). If you want to ignore AC Fail, select 
Option 2 in Location 426. 
 
If AC Fail Reports are not required, 
program Locations 348 and 349 as 0. 
 
15.16  System Status – AC Fail Restore 
Report 
Program the AC Fail Restore Report value in 
Location 350 (tens digit) and Location 351 (units 
digit). 
The default values are 
10 (tens) and 7 (units). 
An AC Fail Restore Report is sent when the AC 
mains supply is connected continuously for longer 
than 2 min.   
 
If AC Fail Restore Reports are not 
required, program Locations 350 and 
351 as 0. 
15.17  System Status – Low Battery Report 
Program the Low Battery Report value in 
Location 352 (tens digit) and Location 353 (units 
digit). 
The default values are 
10 (tens) and 1 (units).