ICP-CC404 | Installation Guide | 16.0   Programmable Outputs 
 
 
64 Bosch 
Security 
Systems, 
Inc. | 12/08 | F01U089401-02
 
Table 50: 
Test Reporting Time Parameters  
 
Location Parameter 
Default 
360 
Hour of day (tens digit) 
361 
Hour of day (units digit) 
362 
Minute of day (tens digit) 
363 
Minute of day (units digit) 
364 
Test Report (tens digit) 
365 
Test Report (units digit) 
366 
Repeat interval in days 
 
A Test Report (Contact ID Event Code 602) is a 
specific signal sent to the base station receiver and is 
normally used to test the dailing and reporting 
functions of the control panel.  
When programming Test Report options, specify the 
hour and minute of the day the report is required, 
and how often to send the report. Test reports are 
sent on a daily basis from every day to every fifteen 
days. Refer to Section 6.1.1 Set the Number of Days until 
the First Test Report
 on page 27 to set the first test 
report. 
 
 
If Test Reports are not required, program 
the repeat interval in Location 366 as 0. 
Program the Test Report Time as 24:00 
to send reports every 30 min. 
 
Example 
To send Test Reports once every seven days at 11:35 
PM, program Locations 360 to 366 as:  
2 3 3 5 7 1 7 
15.22  Test Reporting Dialer Options 
Use 
Location 367 to select whether Test Reports are 
sent to Receiver 1 (the default), Receiver 2, or both, 
Receiver 2 only when Receiver 1 fails, or there is no 
reporting at all. Table 51 lists the reporting options. 
 
Table 51: 
Test Reporting Options 
 
Option Description 
No Test Reports required 
1 Receiver 
Receiver 2 
Receiver 1 and Receiver 2 
Receiver 2 only when Receiver 1 fails 
 
16.0  Programmable Outputs 
The ICP-CC404 Control Panel has four fully-
programmable outputs on the main printed circuit 
board and one programmable output that operates 
the codepad buzzer. The four outputs are set by 
default to operate as horn speaker, fire alarm 
verification, strobe, and internal screamer. 
 
Outputs 1 to 4 do not operate when the 
control panel detects a low battery. 
 
Programmable outputs require four parameters to 
operate correctly. 
 
Table 52: 
Output Parameters 
 
Parameter Description 
Event Type 
The Event Type specifies when an output 
is activated. The Output Event Types are 
listed in Section 16.2. Enter the code for 
the Output Event Type into the two 
corresponding locations for the output. 
Polarity Polarity 
determines whether the output 
operates for the duration of the event, 
pulses for the duration, operates once only 
(one shot), or latches on. The polarity 
options are listed in Table 54 on page 69. 
Time Base/ 
Time 
Multiplier 
The Time Base and Time Multiplier 
parameters determine how long and how 
often the output operates. Refer to Section 
16.4 Output Timing
 on page 70. 
 
 
Table 53: 
Output Programming Defaults 
 
Output   
Default Output Type 
Locations 
Event Code
Polarity 
Time Base 
Time Base Multiplier 
Output 1 
Horn Speaker 
368 to 373 
14 
Output 2 
Fire Alarm with Verification  374 to 379 
10 
Strobe 
Strobe – Reset in 8 hr 
380 to 385 
Relay 
Sirens Running 
386 to 391 
15 
Codepad 
Buzzer 
Entry/Exit Warning and 
Day Alarm 
392 to 397 
13 
 
16.1  Redirecting Outputs to the Codepad 
Buzzer 
Multiple output event types can be directed to the 
codepad buzzer so the buzzer can indicate a number 
of events. 
To redirect an output to the codepad buzzer, select an 
output and program it for the desired Output Event 
Type. If the output is functioning correctly, add 8 to 
the first (tens) digit of the Output Event Type.